OVER / UNDER VOLTAGE DETECTION ADJUSTMENTS

OPTIONAL OVER/UNDER VOLTAGE DETECTION BOARD #35867
(See Appendix A - Page 40 for Board Layout)
NOTE: Adjustments are referenced from the units output.
UNDERVOLTAGE ADJUSTMENT
1. The under voltage adjustment can be adjusted from -1% (118.5 VAC) to -20% (95 VAC). The
standard setpoint is -10% (108 VAC).
2. P2 will adjust the undervoltage set point. One turn on P2 will change the voltage level
approximately 1 volt.
ƒ Clockwise = Increase in Sensitivity.
ƒ Counter-Clockwise = Decrease in Sensitivity.
OVERVOLTAGE ADJUSTMENT
1. The over voltage adjustment can be adjusted from +1% (121 VAC) to +20% (145 VAC). The
standard set point is +10% (132 VAC).
2. P1 will adjust the overvoltage set point. One turn on P1 will change the voltage level
approximately 1 volt.
ƒ Clockwise = Decrease Sensitivity.
ƒ Counter-Clockwise = Increase Sensitivity.
DELAY ADJUSTMENT
1. The delay adjustment can be adjusted for a minimum of 5 cycles to a maximum of 15
seconds. The standard set point is 6 seconds.
2. P3 adjusts the delay.
ƒ All the way Counter-Clockwise = 5 cycles.
ƒ All the way Clockwise = 15 seconds.
After two turns clockwise from the full counter-clockwise position, each turn will approximate ½ second.
|