1.5

Specifications of Main Unit

Item
Execution Speed
Space of Control Program
Program Memory
Sequence Command
Application Command
Flow Chart (SFC) Command
X
Output Contact(DI)
Y
Output Relay(DO)
TR
Temporary Relay
Internal Relay
M
Special Relay
S
Step Relay
T
Timer "Time Up" Status Contact
C
Counter "Count Up" Status Contact
Current
0.01S Time base
Time
TMR
0.1S Time base
Value
Register
1STime base
Current
16-Bit
Counter
CTR
Value
32-Bit
Register
HR
DR
Data Register
HR
ROR
IR
Input register
OR
Output Register
SR
Special System Register
0.1mSHigh Speed Timer register R4152~R4154 (3)
High Speed
Hardware(4 sets) DR4096~DR4110 (4×4)
Counter
Software (4 sets) DR4112~DR4126 (4×4)
Register
Real Time Calendar Register
(Not available in MA model)
XR Index Register
External Interrupt Control
Interrupt
Control
Internal Interrupt Control
0.1mS High Speed Timer (HST)
0.33uS/per Sequence Command
20K Words
FLASH ROM or SRAM+Lithium battery for Back-up
36
326 (126 types)
4
X0~X255 (256)
Y0~Y255 (256)
TR0~TR39 (40)
M0~M799 (800)*
Non-retentive
M1400~M1911 (512)
Retentive
M800~M1399 (600)*
M1912~M2001 (90)
Non-retentive
S0~S499 (500)*
Retentive
S500~S999 (500)*
T0~T255 (256)
C0~C255 (256)
T0~T49 (50)*
T50~T199 (150)*
T200~T255 (56)*
Retentive
C0~C139 (140)*
Non-retentive C140~C199 (60)*
Retentive
C200~C239 (40)*
Non-retentive C240~C255 (16)*
R0~R2999 (3000)*
Retentive
D0~D3999 (4000)
Non-retentive R3000~R3839 (840)*
Retentive
R5000~R8071 (3072)*
Read-only
R5000~R8071 can be configured as ROR,
Register
default setting is (0)*
File Register
F0~F8191 (8192)*
R3840~R3903 (64)
R3904~R3967 (64)
R3968~R4167 (197) R4000~R4095 (96)
R4128 (sec) R4128 (min) R4130 (hour) R4131 (day)
R4132
(month)
V、Z (2), P0~P9 (10)
32 (16 point input positive/negative edges)
8 (1, 2 3, 4, 5, 10, 50, 100mS)
1 (16bits), 4 (32bits, derived from HHSC)
Specification
R4133 (year) R4134 (week)
H1-8
Note
Include Derived Commands
Corresponding to External Digital Input
Point
Corresponding to External Digital Output
Point
Can be configured as retentive type
Can be configured as non-retentive type
S20~S499 can be configured as
retentive type
Can be configured as non-retentive type
T0 ~ T255 Numbers for each time base
can be flexibly adjusted.
Can be configured as non-retentive type
Can be configured as retentive type
Can be configured as non-retentive type
Can be configured as retentive type
Can be configured as non-retentive type
Can be configured as retentive type
When not configured as ROR, it can
serve as normal register (for read/Write)
ROR is stored in special ROR area and
not consume program space
Must save/retrieved via special
commands
Corresponding to external numeric input
Corresponding to external numeric
output
Optional for MA module