7 Error Handling
Cause:
No data found or check sum over data is wrong.
Response:
- Engine cannot be started.
- Governor is operating by default parameters.
Action:
- Check data for correct setting, save parameters and restart control unit by a
reset.
Note:
This error will occur only when adjusting and saving parameters.
3091 ErrLogical
Cause:
Error of data structure.
Response:
- Control cannot be started.
- Governor is operating by default parameters.
Action:
- Check data for correct setting, restart governor by a reset.
- Notify HEINZMANN.
3093 ErrStack
Cause:
Internal programming or computing error, "stack-overflow".
Response:
- Control cannot be started.
- Emergency shutdown.
Action:
- Write down the value of parameter 3897 StackTestFreeBytes and notify
HEINZMANN
- Restart control by a reset.
3094 ErrIntern
3095 ExceptionNumber
3096 ExceptionAddr1High
3097 ExceptionAddr1Low
3098 ExceptionAddr2High
3099 ExceptionAddr2Low
Cause:
Internal programming or computing error, so-called "EXCEPTION" error.
Response:
- Control cannot be started.
- Emergency shutdown.
Action:
- Write down the values of the parameters 3095 ExceptionNumber,
3096 ExceptionAddr1High, 3097 ExceptionAddr1Low,
3098 ExceptionAddr2High and 3099 ExceptionAddr2Low and
notify HEINZMANN.
- Restart control by a reset.
48
3191 SErrLogical
3193 SErrStack
3194 SErrIntern
3195 SExceptionNumber
3196 SExceptionAddr1High
3197 SExceptionAddr1Low
3198 SExceptionAddr2High
3199 SExceptionAddr2Low