3050 ErrFeedback
Cause:
Error in feedback system of actuator, actuator not connected.
Response:
- Governor cannot be put into operation.
- Emergency shutdown.
Actions:
- Check feedback cable to actuator.
- Check actuator, replace if necessary.
- Check error limits for feedback:
1952 FeedbackErrorLow / 1953 FeedbackErrorHigh
3051 ErrFeedback2
Cause:
Error in feedback system of actuator 2, actuator 2 not connected.
Response:
- Governor cannot be put into operation.
- Emergency shutdown.
Actions:
- Check feedback cable to actuator.
- Check actuator, replace if necessary.
- Check error limits for feedback:
1962 FeedbackErrorLow2 / 1963 FeedbackErrorHigh2
Note:
These parameters are implemented only in the PRIAMOS III series.
3052 ErrFeedback3
Cause:
Error in feedback system of actuator 3, actuator 3 not connected.
Response:
- Governor cannot be put into operation.
- Emergency shutdown.
Actions:
- Check feedback cable to actuator.
- Check actuator, replace if necessary.
- Check error limits for feedback:
1972 FeedbackErrorLow / 1973 FeedbackErrorHigh
Note:
These parameters are implemented only in the PRIAMOS III series.