7 Error Handling
Error
3001 ErrPickup1
3002 ErrPickup2
3004 ErrOverspeed
3031 ErrOilPressEcy
3050 ErrFeedback
3051 ErrFeedback2
3052 ErrFeedback3
3056 ErrFeedbackRef
3059 ErrFeedbackAdjust
3060 ErrFeedbackAdjust2
3061 ErrFeedbackAdjust3
3075 ErrClearFlash
3076 ErrParamStore
3077 ErrProgramTest
3078 ErrRAMTest
3089 ErrWatchdog
3090 ErrData
3091 ErrLogical
3093 ErrStack
3094 ErrIntern

7.4 Error Parameter List

The below error parameter list contains descriptions of the causes of each single error and
of the control's response. Furthermore, it lists the appropriate actions to be taken to remove
the respective error.
The errors are stored in the volatile error memory under the parameter numbers 3000 and
higher and (as far as provided) in the permanent error memory under the parameter
numbers from 3100 onward.
The errors are sorted by ascending numbers with the parameter on the left indicating the
actual error as stored in the volatile memory and with the parameter on the right indicating
the one stored as a sentinel in the permanent error memory. As explained above, the
control will only react to actual errors whereas the permanent error memory serves no
other purpose than to accumulate information on the occurrences of errors.
36
Error at pickup 1
Error at pickup 2
Overspeedl
Oil pressure below speed dependent shutdown threshold
Error at feedback of actuator 1
Error at feedback of actuator 2 (PRIAMOS III)
Error at feedback of actuator 3 (PRIAMOS III)
Error at feedback reference of actuator 1
Error at automatic actuator adjustment with actuator 1
Error at auto. actuator adjust. with act. 2 (PRIAMOS III)
Error at auto. actuator adjust. with act. 3 (PRIAMOS III)
Error at erasing the flash memory
Error at saving of the parameters in flash memory
Error during permanent check of programme memory
Error during permanent check of RAM memory
Undefined programme flow, internal programming error
No parameters or check sum over parameters wrong
Error of parameter structure
Stack overflow, internal programming error
Exception, internal programming error
Reason