- Restart governor by a reset.
- Notify HEINZMANN.
3085 ErrVoltage
Cause:
The supply voltage for the governor is not within the permissible range from
18 to 33V.
Response:
- Error message.
- Error is cleared automatically as soon as the voltage is back within the
normal range.
Action:
- Check voltage supply.
3087 ErrCPU 2
Cause:
CPU 2 is out of order.
Response:
- Error message.
Action:
- Notify HEINZMANN.
Note:
These parameters are implemented only in the PRIAMOS series.
3087 ErrMainCheckSum
Cause:
Check-sum of control programme is wrong.
Response:
- Governor cannot be put into operation.
Action:
- Restart governor by a reset.
- Notify HEINZMANN.
Note:
This error will only be displayed by the bootloader.
3089 ErrWatchdog
Cause:
Internal computing error, so-called "Watchdog Error".
Response:
- Governor cannot be put into operation.
- Emergency shutdown.
Action:
- Restart governor by a reset.
- Notify HEINZMANN.
Note:
This error will only be displayed by the bootloader.
3090 ErrData
Programmer PG 02
3185 SErrVoltage
3176 SErrCPU2
3190 SErrData