7 Error Handling
3053 ErrActuatorDiff
Cause:
The difference between set actuator travel and actual actuator travel has
exceeded 10 % of the total actuator travel for more than one second. This
error will occur if the injection pump or the actuator are jamming or are not
connected.
Response:
- Error message.
- Error will be cleared automatically, as soon as the difference is again
below 10 %.
Actions:
- Check injection pump resp. throttle valve, replace if necessary.
- Check mechanical parts (linkage).
- Check cables to actuator.
- Check actuator, replace if necessary.
3054 ErrActuatorDiff2
Cause:
The difference between set actuator travel and actual actuator travel at
actuator 2 has exceeded 10 % of the total actuator travel for more than one
second. This error will occur if the injection pump or the actuator are
jamming or are not connected.
Response:
- Error message.
- Error will be cleared automatically, as soon as the difference is again
below 10 %.
Actions:
- Check injection pump resp. throttle valve, replace if necessary.
- Check mechanical parts (linkage).
- Check cables to actuator.
- Check actuator, replace if necessary.
Note:
These parameters are implemented only in the PRIAMOS III series.
3055 ErrActuatorDiff3
Cause:
The difference between set actuator travel and actual actuator travel at
actuator 3 has exceeded 10 % of the total actuator travel for more than one
second. This error will occur if the injection pump or the actuator are
jamming or are not connected.
Response:
- Error message.
- Error will be cleared automatically, as soon as the difference is again
below 10 %.
42
3153 SerrActuatorDiff
3154 SerrActuatorDiff2
3155 SerrActuatorDiff3
Programmer PG 02
Need help?
Do you have a question about the Programmer 2 and is the answer not in the manual?