quadrant-operation.
- Check reference values and error limits for feeedback
- Programme feedback error limits
1972 FeedbackErrorLow = 0
1973 FeedbackErrorHigh = 65535
store values, restart governor by reset and repeat automatic calibration.
- Set error limits again.
Note:
These parameters are implemented only in the PRIAMOS III series.
3061 ErrDigiIO1
3062 ErrDigiIO2
3063 ErrDigiIO3
3064 ErrDigiIO4
Cause:
Hardware component has detected overload.
Response:
- Error message.
Actions:
- Check digital IOs.
- Clear error.
Note:
These parameters are implemented only in the HELENOS series.
3065 ErrISOCommLine
Cause:
Error at hardware component.
Response:
- Communication is impossible.
Actions:
- Restart governor by reset.
- Notify HEINZMANN.
Note:
These parameters are implemented only in the HELENOS series.
3070 ErrCanBus1
Cause:
The CAN controller for CAN bus 1 reports errors such as BusStatus,
ErrorStatus or DataOverrun. In spite of re-initializing the controller it is not
possible to eliminate the errors permanently.
Response:
- Depending on the specific application.
Action:
- Check CAN module.
- Check CAN connection.
Programmer PG 02
3161 SErrDigiIO1
3162 SErrDigiIO2
3163 SErrDigiIO3
3164 SErrDigiIO4
3165 SErrISOCommLine
3170 SErrCanBus1