Operating elements in the system
4
Operating terminals
4.2 Operating terminals
PT2010-A1
PT2004-A1
20 | 57
'System operating unit (19")'
● EN 54-16-compliant indicator panel for visual and acoustic status
messages and control voice alarms
● Display of system status
● Control of voice alarms
● Fault warning with acoustic warning signal
● Color-coded visual indicators: operation, fault, and alarm
–
Operation: green
–
Fault: yellow
–
Voice Alarm: red
● Color-coded control buttons: control of voice alarms, acknowledges
–
<Start Voice Alarm>: red LED indicator button
–
<Reset Voice Alarm>: black button
–
<Silence Voice Alarm>: green LED indicator button
–
Acknowledge faults: black button
–
Acknowledge acoustic warning and LED test: black button
● 8 predefined visual fault indicators: yellow
–
Power fault
–
Fuse fault
–
Earth fault
–
'PACE-Net' fault
–
'PACE-Bus' fault
–
Amplifier fault
–
Microphone fault
–
Speaker circuit fault
● 8 user-configurable state indicators: yellow
● Potential-free fault contact
● Service socket
● RS485 data transmission ('PACE-Bus')
● Addressable via 4-way SIP switch for 'PACE-Bus' connection
● Design: 19", 2 HU
'System state indicator (19")'
● EN 54-16-compliant indicator panel for visual and acoustic status
messages
● Color-coded visual indicators: operation, fault, and alarm
–
Operation: green
–
Fault: yellow
–
Voice Alarm: red
● Fault warning with acoustic warning signal
● Acknowledge acoustic warning and LED test: black button
● Potential-free fault contact
● Design: 19", 1 HU
A6V10430571_en--_c