Acb (Auxiliary Control Board) Interface; Start-Up; Pre-Start Check; System Operation Check - Carrier 40VMU Series Installation And Maintenance Instructions Manual

Under ceiling/floor indoor unit for variable refrigerant flow (vrf) systems
Hide thumbs Also See for 40VMU Series:
Table of Contents

Advertisement

IMPORTANT: The system can connect 64 indoor units,
with different system addresses. If two indoor units in the
same system have identical addresses, abnormal operation
will occur.
ACB (Auxiliary Control Board) Interface —
ACB interface is a dry contact board that can output up to four
signal controlling devices. Refer to Fig. 15 and 24 for
connecting devices to the ACB interface board
ACB interface
CN50
FAN CTON HTON AUXH
MAX AMPS
1A
MAX VOLTAGE
24V
LEGEND
Auxiliary Control Board
ACB
Output for fan Operation
FAN
Output for Cooling Operation
CTON
Output for Heating Operation
HTON
Output for Auxiliary Heat
AUXH
Fig. 24 —ACB Interface

START-UP

Pre-Start Check —
Once installation is complete, make
the following pre-start checks:
1. All indoor and outdoor units are properly installed.
2. All piping and insulation is complete.
3. All electrical connections (both power and control) are
properly terminated.
4. All condensate drains are installed correctly.
5. The power supply is the right voltage and frequency.
6. The units are properly grounded in accordance with
current electrical codes.
7. Suction and liquid line service valves are in the open
position.
System Operation Check —
and pre-start checks are complete, perform the following steps:
1. Using the remote controller, select cooling or heating
mode to check the operation of the system.
2. While the system is in operation, check the following on
the indoor unit:
a. Switches or buttons on the remote controller are
easy to push.
b. Indicator light is showing normal operation and no
error is indicated.
The
CN51
Once the installation
13
c. Swing mode of air louvers is working (if
applicable to unit).
d. Drain pump operation is normal (if applicable).
e. No abnormal vibration or noise.
3. While the system is in operation, check the following on
the outdoor unit:
a. No abnormal vibration or noise is noticed.
b. Condenser fan is in operation.
c. Indicator light is showing normal operation and no
error is indicated.
NOTE: If the unit is turned off or restarted, there is a time delay
of three minutes for the compressor to start from the time the
power is restored.

MAINTENANCE

CAUTION
When servicing or repairing this unit, use only factory-
approved service replacement parts. Refer to the rating
plate on the unit for complete unit model number, serial
number, and company address. Any substitution of parts or
controls not approved by the factory will be at the owner's
risk and may result in equipment damage.
CAUTION
To avoid equipment damage, do not attempt to reuse any
mechanical or electrical controllers that have been wet.
Replace defective controller.
EVERY 3 MONTHS:
• Check the air filter condition. Clean or replace if
necessary.
EVERY 6 MONTHS:
Follow the 3-month maintenance schedule. In addition:
• Clean condensate tray with suitable cleaning agent.
• Clean the grille and panel, if applicable.
EVERY 12 MONTHS:
Follow the 6-month maintenance schedule. In addition:
• Be sure all electrical connections are secure.
• Check condensate pump operation.
• Check the heating and cooling action to confirm proper
operation.

INDOOR UNIT ADDRESSING

For proper system operation, each indoor unit must have a
unique address set from 0 to 63. When setting an address by
remote controller, the outdoor units, indoor units, and MDC
must be powered on. If FE is displayed on the LED screen or
display board, this unit has no address. After setting all indoor
unit addresses, turn off the power supply to all indoor units to
clear the errors.
Indoor unit addressing can be distributed automatically in the
heat pump system. When dip switch "S6" on the outdoor unit's
main PCB board is set to 00 (default set in factory), indoor
units are set for auto-addressing. When powering on for the
first time, it takes six minutes or more to finish auto-addressing
each indoor unit. The heat recovery system cannot accomplish
this function at this time.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents