Installation; Step 1 - Unpack And Inspect Units; Step 2 - Position The Unit - Carrier 40VMU Series Installation And Maintenance Instructions Manual

Under ceiling/floor indoor unit for variable refrigerant flow (vrf) systems
Hide thumbs Also See for 40VMU Series:
Table of Contents

Advertisement

INSTALLATION

Step 1 — Unpack and Inspect Units —
packaged for shipment to avoid damage during normal transit
and handling. It is the receiving party's responsibility to inspect
the equipment upon arrival. Any obvious damage to the carton
and/or its contents should be reported on the bill of lading and a
claim should be filed with the transportation company and the
factory. The unit should always be stored in a dry place and in
the proper orientation as marked on the carton.
CAUTION
To avoid equipment damage, do not lift unit by the drain
pipe or refrigerant piping. Unit should be lifted using the
mounting brackets.
After determining the condition of the carton exterior, carefully
remove each unit from the carton and inspect for damage.
Check to make sure that items such as accessory kit,
thermostats, controller, etc. are accounted for whether
packaged separately or shipped at a later date. Any damage
should be recorded, a claim should be filed with the
transportation company, and the factory should be notified. In
the event a claim for shipping damage is filed, the unit,
shipping carton, and all packing must be retained for physical
inspection by the transportation company. All units should be
stored in the factory shipping carton with internal packaging in
place until installation.
PROTECTING UNITS FROM DAMAGE Do not apply
force or pressure to the coil, piping, or drain stub-outs during
handling. All units should be handled by the chassis or as close
as possible to the unit mounting point locations.
The unit must always be properly supported. Temporary
supports used during installation or service must be adequate to
hold the unit securely. To maintain warranty, protect units
against hostile environments (such as rain, snow, or extreme
temperature), theft, vandalism, and debris on the jobsite.
Equipment covered in this manual is not suitable for outdoor
installations. Do not allow foreign material to fall into drain
pan. Prevent dust and debris from being deposited on motor,
fan wheels, and coils. Failure to do so may have serious
adverse effects on unit operation, and in the case of motor and
blower assembly, may result in immediate or premature failure.
Failure of any unit caused by deposits of foreign material on
the motor or blower wheels will not be covered by the
manufacturer's warranty. Some units and/or job conditions
may require some form of temporary covering during
construction.
PREPARING JOBSITE FOR UNIT INSTALLATION To
save time and to reduce the possibility of costly errors, set up a
complete sample installation in a typical room at the job-site.
Check all critical dimensions such as pipe, wire, and duct
connections requirements. Refer to job drawings and product
dimension drawings as required. Instruct all trades in their
parts of the installation. Units must be installed in compliance
with all applicable local code requirements.
IDENTIFYING AND PREPARING UNITS Be sure power
requirements match available power source. Refer to the unit
nameplate and wiring diagram.
In addition:
• Check all tags on the unit to determine if shipping screws
are to be removed. Remove screws as directed.
Units are
• Rotate the fan wheel by hand to ensure that the fan can
rotate freely. Check for shipping damage and fan
obstructions. Adjust blower motor as required.
Step 2 — Position the Unit
Units must not be installed where they may be exposed to
potentially explosive or flammable atmosphere. If this
instruction is not followed, a fire or explosion may result,
causing property damage, injury, or loss of life.
Select the unit position with the following points in mind:
• Allow adequate space for installation, service clearance,
piping and electrical connections, and necessary
ductwork. For specific unit dimensions, refer to Table 1
and Fig. 2 and 3. Allow clearance according to local and
national codes.
• Confirm that the ceiling or wall is able to support the
weight of the unit. See Table 1 for nominal weight.
• There should be adequate space between the false ceiling
and unit top for under ceiling units, or between the wall
and the back for floor units, for installation and
maintenance (see Fig. 4).
• Install the unit in a location within the room that allows
uniform air flow in all directions.
Fig. 4 —Spacing from Ceiling or Wall
Select the unit position with the following points in mind:
• The unit should be installed in a position that is suitable
to support the total weight of the unit, refrigerant piping
and condensate.
• Proper access should be provided for maintenance for
refrigerant piping, EEV (electronic expansion valve),
electrical box, and condensate pump. A 2-ft clearance is
recommended all around the unit.
• The unit should be at least 24 in. from a wall or similar
obstruction. See Fig. 5.
5
DANGER
FALSE CEILING
¾ in. min.
AIR OUTLET
WALL
A40-1858
¾ in. min.
AIR OUTLET

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents