Fig. 5 —Distance from Wall or Obstruction
• Do not position where the discharge air could blow
directly on the thermostat.
• The unit should not be positioned directly above any
obstruction.
• The unit must be installed square and level.
• The condensate drain should have sufficient downward
slope (1 in. per 100 in.) in any horizontal run between
unit and drain.
IMPORTANT: Be sure that the ceiling grid is
supported separately from the unit. The ceiling grid
must not be supported by an part of the unit or any
associated wiring or piping work.
Step 3 — Mount the Unit
INSTALLING HANGER BOLTS (UNDER CEILING
MOUNT) — Install the hanger bolts at the locations shown in
Fig. 6. Use 3/8-in. all-threaded rod. For unit weight and
mounting dimensions, see Table 3.
A
Fig. 6 —Hanging Bracket Locations
OBSTRUCTION
24 in.
min.
OBSTRUCTION
24 in.
min.
a40-1859
B
HANGING
BRACKET
Table 3 —Unit Weight and Mounting Dimensions
(Under Ceiling Mount)
40VMU UNIT
WEIGHT (lb)
012
57
015-024
62
030
77
036,048
106
MOUNTING UNIT (UNDER CEILING MOUNT) —
The unit can now be lifted on to the hanging rods for under
ceiling mounting.
1. Use rods and fasteners for under ceiling mount to suspend
the hanging bracket.
2. Secure the hanging brackets in position with locknuts and
washers on both sides. Ensure the threaded rod does not
protrude more than 1 in. below the mounting hole on the
hanging bracket as shown in Fig. 7.
0.8 – 1 in.
Fig. 7 —Mounting the Hanging Bracket
3. Remove the side board and grille from the unit as shown
in Fig. 8 (does not apply to unit size 048).
Fig. 8 —Removing Side Board and Grille
4. Slide the unit backwards onto the hanging bracket until
the mounting hole on the unit lines up with the mounting
hole on the hanging bracket. Secure the unit using
mounting bolts as shown in Fig. 9.
Fig. 9 —Securing Unit To Hanging Bracket
6
DIMENSION (in.)
A
B
35-
/
7-
/
3
7
4
8
35-
7-
3
/
7
/
4
8
47
7-
/
7
8
60-
/
7-
/
3
7
4
8
NUT
WASHER
HANGING
BOLT
HANGING BRACKET
A40-1862
SIDE BOARD
GRILLE
HANGING
BOLT
HANGING
BRACKET
MOUNTING
BOLT