Download Print this page

Wiring - Mitsubishi Electric 800 Series Instruction Manual

600v class specification inverter
Hide thumbs Also See for 800 Series:

Advertisement

Terminal connection diagrams
2

WIRING

2.1
Terminal connection diagrams
Sink logic
Main circuit terminal
Control circuit terminal
Three-phase
AC power
supply
Control input signals
(No voltage input allowed)∗3
Forward rotation start
Reverse rotation start
Start self-holding selection
Multi-speed
selection
Second function selection
Terminal 4 input selection
(Current input selection)
Selection of automatic restart
Contact input common
(Common for external power supply transistor)
Frequency setting signals (Analog)
Frequency setting
potentiometer
1/2W1kΩ∗6
Terminal 4 input
(Current input)
Connector for plug-in option connection
For manufacturer

For the FR-A860-01440 or higher, and when a 75 kW or higher motor is used, always connect a DC reactor, which is available as an option. (To select a DC reactor,
refer to
page
25, and select one according to the applicable motor capacity.)
When connecting a DC reactor, if a jumper is installed across terminals P1 and P/+, remove the jumper before installing the DC reactor. (The jumper is not installed for
the FR-A860-01440 or higher.)

When using separate power supply for the control circuit, remove the jumper between R1/L11 and S1/L21.

The function of these terminals can be changed with the input terminal assignment (Pr.178 to Pr.189). (Refer to

Terminal JOG is also used as the pulse train input terminal. Use Pr.291 to choose JOG or pulse.

Terminal input specifications can be changed by analog input specification switchover (Pr.73, Pr.267). To input a voltage, set the voltage/current input switch OFF. To
input a current, set the voltage/current input switch ON. Terminals 10 and 2 are also used as a PTC input terminal. (Pr.561) (Refer to the Instruction Manual (Detailed).)

It is recommended to use 2 W 1 kΩ when the frequency setting signal is changed frequently.

A brake resistor is provided with the FR-A860-00090 or lower. Connect the provided brake resistor to terminals P3 and PR as required.

Connect a brake resistor across terminals P3 (P/+) and PR. (Terminal PR is equipped in FR-A860-01080 or lower.) Install a thermal relay to prevent overheating and
damage of discharging resistors. (Refer to the Instruction Manual (Detailed).)

The function of these terminals can be changed with the output terminal assignment (Pr.195, Pr.196). (Refer to

The function of these terminals can be changed with the output terminal assignment (Pr.190 to Pr.194). (Refer to

Terminal F/C (FM) can be used to output pulse trains as open collector output by setting Pr.291.

Not required when calibrating the scale with the operation panel (FR-LU08) or the parameter unit (FR-PU07).
NOTE
• To prevent a malfunction due to noise, keep the signal cables 10 cm or more away from the power cables. Also, separate the main circuit cables at the input side from
the main circuit cables at the output side.
• After wiring, wire offcuts must not be left in the inverter. Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean. When drilling mounting
holes in an enclosure etc., take caution not to allow chips and other foreign matter to enter the inverter.
• Set the voltage/current input switch correctly. Incorrect setting may cause a fault, failure or malfunction.
• The terminals S1, S2, SIC, So (SO), and SOC are for manufacturer setting. Do not connect anything to these. Doing so may cause an inverter failure.
Do not remove the shorting wires across terminals S1 and PC, terminals S2 and PC, and terminals SIC and SD. Removing either shorting wire disables the inverter
operation.
6
WIRING
DC reactor ∗1
Jumper
Earth
(Ground)
P1
MC
MCCB
R/L1
S/L2
T/L3
R1/L11
Jumper
∗2
S1/L21
Earth
(Ground)
Control circuit
STF
STR
STP(STOP)
RH
High speed
RM
Middle speed
RL
Low speed
∗4
JOG
Jog operation
RT
MRS
Output stop
RES
Reset
AU
CS
after instantaneous
power failure
SD
PC
24VDC power supply
24V external power
+24
supply input
SD
∗5
Common terminal
10E(+10V)
10(+5V)
3
DC0 to 5V
2
2
DC0 to 10V selectable
DC0 to 20mA
5
1
(Analog common)
DC0 to ±10V
Auxiliary
(+)
1
DC0 to ±5V selectable
(-)
input
DC4 to 20mA
(+)
4
DC0 to 5V
(-)
DC0 to 10V
Connector 1 Connector 2
Connector 3
Shorting
wire
PC
S1
S2
SIC
SD
Brake resistor  ∗7,∗8
R
Earth
(Ground)
P/+
P3
PR
N/-
U
Inrush current
V
limit circuit
W
Main circuit
C1
B1
Relay output 1
(Fault output)
A1
C2
B2
Relay output 2
A2
RUN
Running
SU
Up to frequency
IPF
Instantaneous
power failure
OL
Overload
FU
Frequency detection
SE
Open collector output common
Sink/source common
24V
PU
connector
Voltage/current
input switch
F/C
ON
USB A
OFF
(FM)
∗11
2
connector
4
Calibration
Initial value
resistor ∗12
SD
∗5
USB
mini B
AM
connector
5
Initial value
∗5
TXD+
Initial value
TXD-
selectable
∗5
RXD+
RXD-
GND
(SG)
Terminating
VCC
resistor
So
(SO)
SOC
FR-A860-00320
Brake resistor ∗8
DC reactor ∗1
R
Jumper
P1
P/+
PR
N/-
Motor
M
Earth (Ground)
Relay output∗9
Open collector output∗10
Indicator
+
-
(Frequency meter, etc.)
Moving-coil type
1mA full-scale
(+) Analog signal output
(0 to ±10VDC)
(-)
RS-485 terminals
Data
transmission
Data
reception
GND
5V
(Permissible load current 100mA)
page
17.)
page
17.)
page
17.)

Hide quick links:

Advertisement

loading