Download Print this page

Mitsubishi Electric 800 Series Instruction Manual page 12

600v class specification inverter
Hide thumbs Also See for 800 Series:

Advertisement

Control circuit terminal
2.3
Control circuit terminal
 Terminal layout

This terminal functions as terminal FM.
 Wiring method
• Power supply connection
For the control circuit wiring, strip off the sheath of a cable, and use it with a blade terminal. For a single wire, strip off the sheath of the wire and apply directly.
Insert the blade terminal or the single wire into a socket of the terminal.
(1)
Strip off the sheath for the below length. If the length of the sheath peeled is too long, a short circuit may occur with neighboring wires. If the length is too
short, wires might come off.
Wire the stripped cable after twisting it to prevent it from becoming loose. In addition, do not solder it.
(2)
Crimp the terminals by inserting the wires into a blade terminal.
Insert wires to a blade terminal, and check that the wires come out for about 0 to 0.5 mm from a sleeve.
Check the condition of the blade terminal after crimping. Do not use a blade terminal of which the crimping is inappropriate, or the face is damaged.
• Blade terminals commercially available (as of January 2017)
2
Cable gauge (mm
)
With insulation
0.3
AI 0,34-10TQ
0.5
AI 0,5-10WH
0.75
AI 0,75-10GY
1
AI 1-10RD
1.25, 1.5
AI 1,5-10BK
0.75 (for two wires)
AI-TWIN 2×0,75-10GY

A ferrule terminal with an insulation sleeve compatible with the MTW wire which has a thick wire insulation.

Applicable to terminals A1, B1, C1, A2, B2, and C2.
Blade terminal product
2
Cable gauge (mm
)
0.3 to 0.75
BT 0.75-11
(3)
Insert the wires into a socket.
12
WIRING
∗1
2
5
4
1 F/C
+24 SD
AM
5 10E 10 SE SE
RUN
SU IPF OL FU
Cable sheath stripping length
10 mm
Ferrule terminal model
Without insulation
sleeve
sleeve
A 0,75-10
A 1-10
A 1,5-10
Insulation cap
number
product number
VC 0.75
When using a single wire or stranded wires without a blade terminal, push the open/close button all the
way down with a flathead screwdriver, and insert the wire.
So SOC
SD
SIC
S1 S2 PC
A1
PC RL RM RH RT AU
STP MRS RES
Damaged
Crumpled tip
For UL wire

AI 0,5-10WH-GB
AI 0,75-10GY-GB
Phoenix Contact Co., Ltd.
AI 1-10RD/1000GB
AI 1,5-10BK/1000GB

Manufacturer
NICHIFU Co., Ltd.
B1
C1
A2
B2
C2
SD SD
STF STR JOG
CS
Wires are not inserted
into the sleeve
Crimping tool
Manufacturer
name
CRIMPFOX 6
Crimping tool
product number
NH 69
Open/close button
Flathead screwdriver
Recommended cable
gauge:
2
0.3 to 0.75 mm
Unstranded
wires

Hide quick links: