Specifications - Riello RTC-80 Series Installation, Operation And Service Manual

Table of Contents

Advertisement

1.6.3 Specifications

Description
Boiler category
Maximum allowable working pressure
Maximum allowable working temperature
Water Connections Inlet/Outlet (Flanged)
High Temp. Return Water Connections
Minimum Water Flow (GPM) (*)
Maximum Water Flow (GPM) (*)
Water Volume (Gal) (*)
Water Pressure Drop
Maximum turndown (Nat.Gas)
Vent Connections
Vent Materials
Type of Fuel (**)
NOx Emissions <30ppm Capability on Nat. Gas
Temperature Control Range
Ambient Temperature Range
Standard Listings & Approvals
Water capacity (Gal) (*)
Weight (dry) Ibs. (without paneling)
Shipping Weight Ibs. (without paneling)
Weight of paneling lbs.
Weight (wet) Ibs. (with paneling)
(*)
Units shown are in US Gallons.
(**)
Other fuels may be used. For alternate fuels not listed, please contact factory.
(***)
Using #2 Fuel Oil, the boiler return temperature must not be lower than 140 °F (non-condensing operation).
1000
1300
1700
80 psi
80 psi
80 psi
210°F
210°F
210°F
2-1/2"
3"
4"
2"
2-1/2"
3"
12
15
20
130
160
200
130.7
146.6
196.2
0.67 psi
0.49 psi
0.44 psi
at 95
at 124
at 162
GPM (*)
GPM (*)
GPM (*)
10:1
10:1
10:1
10"
10"
12"
AISI 316L AL29-4C (29% Cr - 4% Mo)
Natural Gas, Propane, #2 Fuel Oil (***)
130.7
146.6
196.2
1676
1786
2679
1720
1841
2756
132
154
198
2899
3164
4515
9
RTC-80
2300
3000
3800
ASME Section IV
80 psi
80 psi
80 psi
210°F
210°F
210°F
4"
5"
5"
3"
3"
3"
30
40
50
290
370
480
203.4
348.7
368.5
1.86 psi
1.76 psi
1.36 psi
at 219
at 285
at 361
GPM (*)
GPM (*)
GPM (*)
10:1
10:1
10:1
12"
14"
14"
yes
80°F to 195°F
32°F to 140°F
ASME, ETL, AHRI
203.4
348.7
368.5
2965
4167
4777
3097
4334
4956
264
308
352
4927
7385
8206
GENERAL
4700
5500
80 psi
80 psi
210°F
210°F
6"
6"
4"
4"
60
70
580
690
482.1
501.9
1.45 psi
2.18 psi
at 447
at 523
GPM (*)
GPM (*)
10:1
10:1
16"
18"
482.1
501.9
5908
6834
6085
7028
473
506
10406
11530