Functions
7.11 3RW5 HMI Standard
Measured values
Parameter list
144
Display
Explanation
LOCL
Manual mode
CNTRL
REMT
Automatic
CNTRL
Display
Explanation
...A
The average of the 3 phase currents is displayed in amps.
I AVG
...A
Current measured value phase L1 is displayed in amps.
I L1
...A
Current measured value phase L2 is displayed in amps.
I L2
...A
Current measured value phase L3 is displayed in amps.
I L3
Display
Explanation
..
Current limiting value as a multiple of the set rated operational current I
xIe
motor.
...%
Starting voltage
U ON
...s
Ramp up time
t ON
...s
Stopping time
t OFF
...
Tripping class for motor overload protection
CLASS
...A
Rated operational current I
Ie
....
AUTO
RMode
MAN
REMT
...
Station address for PROFIBUS (only displayed if a "PROFIBUS" communication
module is being used)
PBADR
...
Station address for Modbus (only displayed if a "Modbus RTU" communication
module is being used)
MODBS
CNTRL (CONTROL)
The master control function is with the 3RW5 HMI Standard
("Manual operation local - HMI controlled" mode).
Master control function is not with the 3RW5 HMI Standard.
To make the unit the master control, press the LOCAL /
REMOTE key. Refer to Chapter Operating modes and master
control function (Page 15).
of the motor
e
Auto RESET
Manual RESET
Remote RESET
Manual, 09/2019, A5E35628455002A/RS-AA/001
of the
e
SIRIUS 3RW50 soft starter