● Continue to screw the screws into the fixing brackets
at the front. Fasten the fixing brackets onto the 3RW5 HMI High Feature
● Tighten the 3RW5 HMI High Feature with a tightening torque of 0.3 ... 0.35 Nm
Ensure that all of the screw heads are in contact with the fixing bracket.
Procedure for connecting with the HMI connecting cable
● Observe the coding of the plug and socket
● Lock the connector in the socket
● The HMI connecting cable in the cable duct of the 3RW5 HMI High Feature may only be
routed downward.
Make sure that you install the cable in accordance with EMC requirements. For example,
route data cables separately from the motor cable. Connect both sides of shielded cables
over a large surface area.
SIRIUS 3RW50 soft starter
Manual, 09/2019, A5E35628455002A/RS-AA/001
.
.
Mounting and dismantling
3.4 Connecting the 3RW5 HMI
until they protrude approx. 8 mm
.
.