Messages and diagnosis
8.4 Faults and remedial actions of the 3RW50 soft starter
Error
Error
No.
1)
1408
Zero current after ON
command
1409
Loss of phase L1
1410
Loss of phase L2
1411
Phase failure L3
1417
Bypass defective
1418
Bypass protective
shutoff
1454
Module slot wrong or
configuration faulty
1466
Contact 1 failed
1468
Contact 3 failed
170
Cause
No current flow is detected
after the motor feeder is
switched on. Possible
causes:
Main circuit interrupted
•
(fuse, circuit breaker)
Motor contactor or
•
contactor control is
defective
No load
•
The main power monitoring
detects a phase failure.
Bypass defective
•
The error can also be
•
generated by
successive, brief
interruptions of the
control supply voltage.
An excessively high current
has occurred in bypass
mode.
There is a difference
between a real slot and a
slot configured in the
SIRIUS Soft Starter ES
(TIA Portal).
Switching element defective •
Remedy
Acknowledgment once
•
the cause has been
rectified.
Acknowledgment once
•
the cause has been
rectified.
Check the bypasses for
•
L1, L2 and L3 and
replace any that are
defective.
Please contact Technical
•
Support (Support
Request (Page 37)).
Check the motor.
•
Check the dimensioning
•
of the soft starter.
Acknowledgment after
•
cooling down
Ensure consistency
•
between plugged and
configured module.
Possibly the referenced
module has a wiring error.
After the cause is
•
eliminated, the error
self-acknowledges.
Check the contact blocks
for L1, L2, and L3 and
replace any that are
defective.
Please contact Technical
•
Support (Support
Request (Page 37)).
Manual, 09/2019, A5E35628455002A/RS-AA/001
RESET MODE
Manual
Remote
Auto
2)
3)
x
x
-
x
x
-
-
-
-
x
x
-
-
-
-
-
-
-
SIRIUS 3RW50 soft starter
4)