Delta DVP02DA-E2 Instruction Sheet page 5

Analog output module
Hide thumbs Also See for DVP02DA-E2:

Advertisement

CR#
Attrib.
#34
O R/W Adjusted Gain value of CH1
#35
O R/W Adjusted Gain value of CH2
#36
O R/W Adjusted Gain value of CH3
#37
O R/W Adjusted Gain value of CH4
Function: Set value changing
#40
O R/W
prohibited
Function: Save all the set
#41
X R/W
values
Function: Return to default
#42
X R/W
setting
#43
X
R
Error status
Function: Enable/Disable limit
#100 O R/W
detection
#101 X R/W Upper and lower bound status
#102 O R/W Set value of CH1 upper bound
#103 O R/W Set value of CH2 upper bound
#104 O R/W Set value of CH3 upper bound
#105 O R/W Set value of CH4 upper bound
#108 O R/W Set value of CH1 lower bound
#109 O R/W Set value of CH2 lower bound
#110 O R/W Set value of CH3 lower bound
#111 O R/W Set value of CH4 lower bound
#114 O R/W Output update time of CH1
#115 O R/W Output update time of CH2
#116 O R/W Output update time of CH3
#117 O R/W Output update time of CH4
#118 O R/W LV output mode setting
Symbols:
O: When CR#41 is set to H'5678, the set value of CR will be saved.
X: set value will not be saved.
R: able to read data by using FROM instruction.
W: able to write data by using TO instruction.
CR#43: Error status value. See the table below:
bit0
K1 (H'1)
bit1
K2 (H'2)
bit2
K4 (H'4)
bit9
K512(H'0200)
Note: Each error status is determined by the corresponding bit (b0 ~ b13) and there may be more
than 2 errors occurring at the same time. 0 = normal; 1 = error
Register name
Description
Power supply error
bit11 K2048(H'0800)
Hardware error
bit12 K4096(H'1000)
Upper / lower
bit13 K8192(H'2000)
bound error
Mode setting error
- 4 -
Explanation
Set the adjusted Gain value of CH1 ~ CH4.
Default = K16,000.
Definition of Gain:
The corresponding voltage (current) input
value when the digital output value = 16,000
Prohibit set value changing in CH1 ~ CH4.
Default= H'0000.
Save all the set values. Default =H'0000.
Set all values to default setting. Default =
H'0000
Register for storing all error status. Refer to
table of error status for more information.
Enable/Disable the upper and lower bound
detection function. Default= H'0000.
Display the upper and lower bound value.
Default =H'0000.
Set value of CH1~CH4 upper bound. Default
= K32000.
Set value of CH1~CH4 lower bound. Default
= K-32000.
Set value of CH1~CH4 lower bound. Default
=H'0000.
Set the output mode of CH1~CH4 when the
power is at LV (low voltage) condition.
Default= H'0000.
Upper / lower bound
setting error
Set value changing
prohibited
Communication
breakdown on next