socomec COUNTIS E23 Instruction Manual

socomec COUNTIS E23 Instruction Manual

Three-phase energy meter direct - 80 a modbus
Hide thumbs Also See for COUNTIS E23:

Advertisement

INSTRUCTION MANUAL
EN
COUNTIS E23/E24
Three-phase energy meter
Direct - 80 A MODBUS
COUNTIS E23
COUNTIS E24 - MID
www.socomec.com/en/countis-e2x

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the COUNTIS E23 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for socomec COUNTIS E23

  • Page 1 INSTRUCTION MANUAL COUNTIS E23/E24 Three-phase energy meter Direct - 80 A MODBUS COUNTIS E23 COUNTIS E24 - MID www.socomec.com/en/countis-e2x...
  • Page 2: Table Of Contents

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31 COUNTIS E23/E24 - 545877A - SOCOMEC...
  • Page 3: Documentation

    1. DOCUMENTATION All documentation on the COUNTIS E23/E24 is available on the website at the following address: www.socomec.com/en/countis-e2x COUNTIS E23/E24 - 545877A - SOCOMEC...
  • Page 4: Hazards And Warnings

    The assembly, use, servicing and maintenance of this equipment must only be carried out by trained, qualified professionals. SOCOMEC shall not be held responsible for failure to comply with the instructions in this manual. 2.1. Risk of electrocution, burns or explosion •...
  • Page 5: Preliminary Operations

    • The unit has not been damaged during transportation • The device reference number conforms to your order • The package includes: - 1 device - 1 sealing kit (for COUNTIS E24) - 1 Quick Start guide COUNTIS E23/E24 - 545877A - SOCOMEC...
  • Page 6: Introduction

    4.1. Introducing the COUNTIS E23 / E24 The COUNTIS E23 and E24 are modular active and reactive electrical energy meters that display consumed energy. They are designed for three-phase networks and allow a direct connection of up to 80 A. They are equipped with a MODBUS communication Bus.
  • Page 7: Lcd Display

    12. Tariff display 13. Energy balance 14. Inductive value 15. Capacitive value 16. Imported ( ) or exported energy or power ( 4.5. Dimensions Dimensions: in/mm 2.83 2.83 0.24 0.24 1.73 1.73 2.52 2.52 COUNTIS E23/E24 - 545877A - SOCOMEC...
  • Page 8: Electrical Values Measured

    NOTE: ∑ is the sum of the meter readings for each phase, divided by 3. 4 .6 .2 . Energy balance; definition Energy balance Formula (+kWh T1) – (-kWh T1) + (+kWh T2) – (-kWh T2) kvarh (+kvarh T1) – (-kvarh T1) + (+kvarh T2) – (-kvarh T2) COUNTIS E23/E24 - 545877A - SOCOMEC...
  • Page 9: Installation

    • Avoid vibrations with accelerations greater than 1 g for frequencies lower than 60 Hz. 5.2. DIN rail mounted The COUNTIS E23/E24 can be mounted on a 35-mm DIN rail (EN 60715TM35). They must be used inside electrical cabinets. COUNTIS E23/E24 - 545877A - SOCOMEC...
  • Page 10: Connection

    -> 35 mm 0.47" / 12 mm 17.70 lb.in / 2 Nm max. 6.2. Connection to the electrical network and to the loads The COUNTIS E23/E24 are intended for three-phase networks with neutral. COM RS485 MODBUS T1/2 NC - + MODBUS 1: NC (not connected).
  • Page 11: Mid Compliance

    The information provided via the RS485 COM is transmitted for information only and has no legal value. • MID Declaration of Conformity The MID Declaration of Conformity is available on the website: www.socomec.com/en/countis-e2x seal COUNTIS E23/E24 - 545877A - SOCOMEC...
  • Page 12: Communication

    8. COMMUNICATION 8.1. General information The Modbus communication available on the COUNTIS E23/E24 communicates via an RS485 series link (2 or 3 wires) which is used to operate devices from a PC or an API. In a standard configuration an RS485 connection is used to connect 32 devices to a PC or a controller over 1200 metres.
  • Page 13: Communication Structure

    To comply with the Modbus protocol, the inter-character time must be ≤ 3 silences. This means the time for 3 characters to be emitted so that the message is processed by the COUNTIS E23/E24. In order to use the information correctly, you must use the Modbus functions in accordance with the codes: •...
  • Page 14: Configuration

    9. CONFIGURATION The device can be configured directly from the COUNTIS E23/E24 screen in programming mode or via the communication link. The paragraphs below describe configuring using the screen. 9.1. Onscreen configuration From the screen, go to programming mode to change your communication settings. How to browse through the...
  • Page 15: View All Of The Menu "Setup 2

    Ea+ partial (kWh) Tariff T1, T2 Ea+ partial (kWh) Ea- partial (kWh) Tariff T1, T2 Ea- partial (kWh) Eap partial (kVAh) Er+ partial (kVarh) Er- partial (kVarh) Return to the first menu screen, "SETUP 2" COUNTIS E23/E24 - 545877A - SOCOMEC...
  • Page 16: Detailed View Of Menu "Setup 2

    1, 2 Reset energies Ea+ partial Tariff T1, T2; Ea+ partial; Ea- partial Tariff T1, T2; Ea- partial; Eap partial; Er+ partial; Er- partial Return to the first menu screen, "SETUP 2" XX = default value COUNTIS E23/E24 - 545877A - SOCOMEC...
  • Page 17: Example: Setting The Communication Address

    9 .1 .4 . Example: setting the communication address In "SETUP 2" mode (see page 14), go to the "Addr communication address" screen Example: changing the communication address to 247. >3s Baudrate Modbus Parity Modbus Stop bits All partial counters reset COUNTIS E23/E24 - 545877A - SOCOMEC...
  • Page 18: Use

    Go back to first screen, menu and exported screen, menu screen, menu "rt" "tot" reactive energy "info" ______________ Active energy bal- ance ______________ Reactive energy balance ______________ Go back to first screen, menu "Par.b" COUNTIS E23/E24 - 545877A - SOCOMEC...
  • Page 19: Detailed View Of The Menu For Tariff 1, "Tar.1

    Imported inductive reactive energy, tariff 1 Go back to first screen, menu "Tar.1" Exported inductive reactive energy, tariff 1 Imported capacitive reactive energy, tariff 1 Exported capacitive reactive energy, tariff 1 Imported reactive energy, tariff 1 COUNTIS E23/E24 - 545877A - SOCOMEC...
  • Page 20: Detailed View Of The Menu For Tariff 2, "Tar.2

    Imported inductive reactive energy, tariff 2 Go back to first screen, menu "Tar.2" Exported inductive reactive energy, tariff 2 Imported capacitive reactive energy, tariff 2 Exported capacitive reactive energy, tariff 2 Imported reactive energy, tariff 2 COUNTIS E23/E24 - 545877A - SOCOMEC...
  • Page 21: Detailed View Of The Total Menu, "Tot

    L1, L2, L3, ∑ ∑ Total imported inductive reactive energy Go back to first screen, menu "tot" ∑ Total exported inductive reactive energy ∑ Total imported capacitive reactive energy ∑ Total exported capacitive reactive energy ∑ COUNTIS E23/E24 - 545877A - SOCOMEC...
  • Page 22: Detailed View Of The Menu Showing Partial Readings And The Energy Balance "Par.b

    Exported partial active energy for tariff T1 ∑ Reactive energy balance Exported partial active energy for tariff T2 ∑ Partial exported active energy Go back to first screen, menu "Par.b" ∑ Partial apparent energy ∑ COUNTIS E23/E24 - 545877A - SOCOMEC...
  • Page 23: Starting Up The Partial Energy Meter

    10 .4 .1 . Starting up the partial energy meter Y=OK N=Cancel x1 Confirm 10 .4 .2 . Stopping the partial energy meter Y=OK N=Cancel x1 Confirm 10 .4 .3 . Resetting the partial energy meter to zero >3s Y=OK N=Cancel x1 Confirm COUNTIS E23/E24 - 545877A - SOCOMEC...
  • Page 24: Detailed View Of The Menu For Realtime Readings, "Rt

    L1, L2, L3, ∑ Realtime reactive power Go back to first screen, menu "rt" L1, L2, L3, ∑ Realtime phase/phase voltage ∑ Realtime phase/neutral voltage ∑ Realtime three-phase current ∑ Realtime power factor ∑ COUNTIS E23/E24 - 545877A - SOCOMEC...
  • Page 25: Detailed View Of The Menu "Info

    10.6. Detailed view of the menu "info" Metrological firmware version Non-metrological firmware version Checksum of metrological firmware Checksum of non-metrological firmware Installed communication port Go back to first screen, menu "info" COUNTIS E23/E24 - 545877A - SOCOMEC...
  • Page 26: Diagnostics Messages

    • If a 123 phase sequence is detected, the symbol appears. • If a 132 phase sequence is detected, the symbol appears. 11.3. Malfunction • If you see this message, the meter has malfunctioned and must be replaced. COUNTIS E23/E24 - 545877A - SOCOMEC...
  • Page 27: Assistance

    Solutions Device not working Check the neutral and phase 1 cable connections. Phases not shown onscreen Check the connections Phases reversed onscreen Check the network configuration Error message Check the meter is working OK COUNTIS E23/E24 - 545877A - SOCOMEC...
  • Page 28: Characteristics

    Total and partial reading MID metering Bidirectional with three-phase Resolution 10 Wh, 10 varh ENERGY ACCURACY Class B (EN 50470-3) E24 Active energy Ea+ Class 1 (EN 62053-21) Reactive energy Er+ Class 2 (EN 62053-23) COUNTIS E23/E24 - 545877A - SOCOMEC...
  • Page 29 SELV Load unit SAVING Energy registers In FRAM memory ENVIRONMENTAL CONDITIONS Mechanical environment Electromagnetic environment Operating temperature range -25°C to +55°C Storage temperature -25°C to 75°C Humidity ≤ 80% Installation Internal (box/cabinet) Vibrations ±0.075 mm COUNTIS E23/E24 - 545877A - SOCOMEC...
  • Page 30 Modular - width of 4 modules (DIN 43880) 72 x 90 x 64 Mounting On DIN rail (EN 60715) Connection capacity, tightening torque See chapter "6. Connection", page 10 Protection index Front: IP51 - casing: IP20 Insulation class Class II (EN 50470-1) Weight 440 g COUNTIS E23/E24 - 545877A - SOCOMEC...
  • Page 31: List Of Abbreviations

    Frame stop bit 1 stop bit 2 stop bits Reset partial energy ConF? Confirm selection Save and exit Exit without saving Continue without saving Tariff management option Tariff management via communication Tariff management via device input COUNTIS E23/E24 - 545877A - SOCOMEC...
  • Page 32 CORPORATE HQ CONTACT: SOCOMEC SAS 1-4 RUE DE WESTHOUSE 67235 BENFELD, FRANCE www.socomec.com 545877A...