Eaton Cutler-Hammer Ampgard SC9000 Instructions Manual page 13

36" wide vacuum-break starters rated 360 amperes, 7200 volts, slide-out type
Table of Contents

Advertisement

I.B. 48003
7
Free the isolating switch (H), by
removing two hex head bolts as
shown.
10
Refer to load cable instruction
tag located at motor terminals
(M) for load wiring instructions.
Controller is now ready to wire,
both line and load.
Effective 11/97
8
Pull the isolating switch forward.
CAUTION: It has no latch and will
pull completely out. However, it
weighs only 75 lbs. (34 kilograms)
and can usually be handled
without a crane or lift.
11
After wiring, reverse the
procedure to reassemble. Slide
the isolating switch in place and
secure with two bolts. Refer to
Steps 7 and 8.
9
If no vertical bus bars are present
and cable is used to connect
power to the line stabs, loosen
four pan head screws holding the
barrier and shutter assemble
approximately three turns. Lift the
assembly up and off the screws.
Disconnect the shutter drive lever
using the keyhole in the lever.
12
Check to make sure each fuse
clamp is in correct position in fuse
locator. Refer to instructions on
the lower door.