36" wide vacuum-break starters rated 360 amperes, 7200 volts, slide-out type
Table of Contents

Advertisement

Page 12
1
Remove the two positioning bolts
(A). Free the clevis attached to
the mechanical interlock arm.
See Figure 8 on Page 6. Save
all hardware.
4
Disconnect the auxiliary contact
terminal blocks (H) on the
isolating switch.
2
Remove three power circuit fuses
(B) using the fuse puller (K)
supplied. See operating
instructions inside medium-
voltage door (C).
5
Remove contactor (E) with a
sharp pull forward.
3
Separate the contactor side of the
control wires from the terminal
block (D).
6
Part way out the contactor will
reach a balanced position. Lower
the contactor to the floor and slide
it out of the way. The contactor
weighs approximately 160 lbs. (73
kilograms). If a contactor is
installed in an upper compartment,
an industrial lift with a platform is
necessary.
I.B. 48003
Effective 11/97