Model 1001A Installation and Operation Manual
Electrical Conduit
1. Choose the location for the enclosure's electrical conduit
connection(s) based on the requirements on page 15,
"Electrical Supply Requirements".
2. Drill and deburr enclosure conduit fi tting holes in the
protected enclosure. Mount the fi ttings.
3. Determine appropriate route for the enclosure electrical and
power alarm signal conduit.
4. Measure, cut and thread conduit, check conduit fi t to insure
proper seating. Fully ream all conduit.
5. Install conduit and tighten all fi ttings to fi tting manufacturers
specifi cations. Secure conduit to appropriate structural
supports as required.
6. Seal all conduit with an approved compound prior to
operation of the protection system.
HELPFUL HINT
It may be impractical to pour all electrical conduit seals
prior to installation in the fi eld. However, all conduit
connections must be sealed for proper testing and
operation of the enclosure protection system. Therefore,
the use of temporary seals such as duct seal or masking
tape for bench or shop testing, prior to fi nal fi eld
installation may be used.
Switch
body
Setpoint
calibration
screw
Grounding
screw
1/2" conduit
port
WPS Style EXP Pressure Switch
with Cover Removed
Switch
body
Setpoint
calibration
screw
Grounding
screw
1/2" conduit
port
WPSA Style EXP Pressure Switch
with Cover Removed
16

Conduit Installation

WPS & WPSA Style Conduit
WPS and WPSA style systems provide electrical contacts
for audible or visual alarm devices that signal a loss of
protected enclosure pressure. WPS and WPSA style systems
are calibrated to alarm at 0.15" for Class I applications and
0.50" for Class II applications. The switches are suitable
for hazardous (classifi ed) outdoor locations. Wiring must
be installed with a seal and conduit fi ttings suitable for the
area. Alarm circuit power may be derived from the protected
enclosure power source or an intrinsically safe alarm signal
source. All associated alarm devices must be protected by
suitable means (explosion-proof, purged, or intrinsically safe).
WPS & WPSA Style Conduit Connection Parts
Fitting Kits Can Be Factory Furnished
1. For WPS and WPSA Style EXP pressure loss alarm switch
connected to an enclosure mounted alarm, one (1) LCK (L
fi tting conduit kit) or equivalent conduit elbow, coupling and
seal fi ttings.
2. For WPS and WPSA Style EXP pressure loss alarm switch
connected to a remote mounted alarm, one (1) TCK (T fi tting
conduit kit) or equivalent conduit tee, coupling and seal
fi ttings.
3. One (1) lot 150# rating 1/2" galvanized or aluminum pipe.
Electrical
switch
contacts
Low port
sintered
vent
High port
tube
fi tting
Low port
sintered
vent
120 VAC
power &
electrical
switch
contacts
High port
tube
fi tting
TCK "T" Fitting Conduit Kit