Model 1001A Installation and Operation Manual
1/2"
PROTECTIVE
GAS SUPPLY
HEADER
Description
Tubing or pipe diameter
Maximum tubing / pipe length and
maximum number of bends / elbows
1/2"
PROTECTIVE
GAS SUPPLY
HEADER
A
*NOTE: Tube and pipe sizes are trade sizes and are not equal in inside
diameter. DO NOT substitute tube for pipe with same trade size.
HELPFUL HINTS
To ensure adequate protective gas fl ow to the protected enclosure(s), all piping and tubing must be fully reamed.
Precautions must be taken to prevent crimping and other damage to protective gas piping and tubing.
When protecting multiple enclosures with a single enclosure protection system, the enclosures must be
connected in series from the smallest to the largest to ensure adequate protective gas fl ow.
Determining Enclosure Inlet & Outlet Connection Locations
INLET
OUTLET
Connections for heavier than
air gases and vapors
INLET
6

Getting Started

Typical Single Protected Enclosure Connections
C
REFERENCE
ENCLOSURE
PROTECTION
SYSTEM
SUPPLY
A
B
A
System
supply tubing
1/4" O.D. tubing
1/4" O.D. tubing
fully reamed
20 feet
10 bends
Typical Multiple Protected Enclosure Connections
B
PROTECTED
SUPPLY
ENCLOSURE
ENCLOSURE
PROTECTION
SYSTEM
REFERENCE
OUTLET
Connections for lighter than
air gases and vapors
ENCLOSURE PROTECTION VENT
(Optional)
PROTECTED
ENCLOSURE
E
C
B
Enclosure
Enclosure
reference
supply
1/4" O.D. tubing
fully reamed
fully reamed
5 feet
20 feet
5 bends
10 bends
D
PROTECTED
ENCLOSURE
C
HELPFUL HINTS
If fl ammable gases are lighter than air, the inlet connection
to each enclosure must enter near a bottom corner. The
outlet connection, for an optional enclosure protection
vent or piping to an adjacent protected enclosure, must
exit near an extreme opposite top corner.
If fl ammable gases are heavier than air, inlet and outlet
connections must be reversed.
In all cases, the most prevalent gas must determine the
location of inlet and outlet connections.
D
E
Multi - enclosure
Optional remote
connections
venting
1/2" I.D. pipe
1/2" I.D. pipe
fully reamed
fully reamed
10 feet
30 feet
5 elbows
5 elbows
D
PROTECTED
ENCLOSURE