Technical Specifications
Safety Device
Signal Connection
Appearance
Net Weight
Packaging
Operating Conditions
2
Max. Sound Level *
Max. Duct Equivalent
Length
Operating Environment
IP Number
Design Lifetime of Product *
Specifications are subject to change without notice.
*1: Rating condition: 95°F (35°C) at 60% RH
*2: Measured at 3 ft (1.0m) from surface of the unit
*3: 17,500 hours: (10 hours/day x 250 days) x 7 years
ITEM
Internal Overload Relay for
Compressor
Anti-Freezing Thermostat for
Evaporator
Fire Alarm lnput
Warning Signal Output
Paint color
Dimensions - W x D x H
Dimensions - W x D x H
Weight
Min.
Max.
With Condenser Duct
high/mid/low
Without Condenser Duct
high/mid/low
Per Cold Duct Hose
Hot Duct Hose
3
11
SPECIFICATIONS
302°F ± 9°F (150°C ± 5°C)
86 amps
On: 60°F ± 1.8°F (16°C ± 1°C)
Off: 27°F ± 1.8°F (-3°C ± 1°C)
No voltage contact input
Contact resistance:
less than 100 ohm
2 amps at 30V (DC/AC)
max. with resistive load
Black
31 x 55 x 64 in
584 lb
34 x 59 x 69 in
666 lb
65°F (18°C), @ 50% RH
105°F (41°C), @ 50% RH
69/68/67 dB(A)
71/70/69 dB(A)
40 ft
100 ft
Indoor
IPX1
7 years or 17,500 hours,
whichever is shorter