Messages on the Display (Page 21)
ID
Symbol
Status line
6t
-
6U
MANUAL
L
-
LP
-
See also
QUICK START [01] (Page 26)
SETUP [20] (Page 27)
SIPART PS100
Operating Instructions, 10/2018, A5E45863537.-AA
8.2 Info IDs, error messages and corrective measures
Meaning / cause
● Control deviation
● Insufficient supply of compressed
air
● Mounting kit not correctly mounted
● Valve blocked
Device in manual mode
Button lock is activated.
Digital input (DI) is activated.
Setting in parameter "BEHAVIOR
DI[22]>BUTTN"
Parameters and device functions are
write-protected with a user PIN.
Remedy
Eliminate the cause.
Switch with
to "AUTO" mode.
Switch the digital input (DI).
Disable the write protection with user PIN
LOCK 2457.