Control System
Components
1A15, 1A16, 1A17, 1A21 Dual Analog
Input/output Module;
Analog Output: The Analog Output is
a voltage only signal. 2-10 Vdc at
22mA
J2: 14 - 26 AWG with a maximum of
two 14 AWG
J2-1 Output #1 to J2-3 (Ground), J2-4
Output #2 to J2-6 (Ground).
Recommended Length to Run external Output signals
Gauge
Ohms per Feet
14
0.00 2823
16
0.004489
18
0.007138
20
0.01135
22
0.01805
24
0.0287
26
0.04563
28
0.07255
Note: the above table is for copper conductors only.
Analog Input:
The analog input can be software
switched between a voltage input or
a current input. When used as a
current input a 200 Ohm load resistor
is switched in.
2-10 Vdc or 4-24 mA Analog Inputs
UCP accepts either a 2-10 Vdc or 4-20
analog input suitable for customer
external control. The type is
determined at unit commissioning
during feature installation.
J2: 14 - 26 AWG with a maximum of
two 14 AWG
J2-2 Input #1 to
J2-3 (Ground).
J2-5 Input #2 to
J2-6 (Ground).
Power, 24 +/- 10 percent VDC, 60 mA
maximum, Trane IPC3 protocol.
UCP provides a 2-10 Vdc analog
signals as Outputs. The Output's
maximum source capability is 22mA.
The maximum recommended length
to run this signal is included in the
table below.
Length (Feet)
Maximum Length (Meters)
1062.7
668.3
420.3
264.3
166.3
104.5
65.7
41.4
324
203.8
128.1
80.6
50.7
31.9
20
12.6