Advertisement

5. Operation
5.3. Transmitter PV display
For Pressure
The upper and lower calibration points indicate the upper and lower pressure value that will correspond the
upper and lower scale value respectively.
Flow = (scale EU100 – scale EU0) * sqroot(( DP – Cal Lower) / (Cal Upper – Cal Lower)) – scale EU0 for
DP > cal Lower
Flow = (scale EU100 – scale EU0) * sqroot((Cal Lower - DP) / (Cal Upper – Cal Lower)) – scale EU0 for
DP < -cal Lower
Flow = 0 for DP < abs ( cal lower)
Where scale EU100 and scale EU0 are in flow units and Cal Upper and Cal Lower are in pressure units.
The square root function is automatically employed for conversion from pressure to flow scale units.
Calibration units are always in pressure units.
20
OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual
Pressure
Description
INH20
INH20_4C
INH20_68f
MMH20
MMH20_4C
MMH20_68F
FTH20
FTH20_4C
FTH20_68F
INHG
INHG_0C
MMGH
MMGH_0C

Table 5-4 XYR 6000 Flow units

FLOW
Description
CMPS
cubic meters per second
CMPM
cubic meters per minute
CMPH
cubic meters per hour
CMPD
cubic meters per day
LPS
liters per second
LPM
liters per minute
Inches H2O
Inches H2O referenced to 4˚C
Inches H2O referenced to 68˚F
millimeters H2O
millimeters H2O referenced to 4˚C
millimeters H2O referenced to 68˚F
Feet H2O
Feet H2O referenced to 4˚C
Feet H2O referenced to 68˚F
Inches mercury
Inches mercury referenced to 0˚C
millimeters mercury
millimeters mercury referenced to 0˚C
Revision 3