Advertisement

A.5
Configuring Smart Meter Using Pushbuttons,
Transmitter Output
Conformity and Smart
Meter Configuration,
continued
60
• If you select pressure type engineering units, you cannot set the
lower or upper display limits. These values are automatically set
when you select the engineering units.
• You can set only the upper display limit when the transmitter is
configured for SQUARE ROOT output conformity. The lower
display limit is fixed at zero (0) for a transmitter in square root
mode and cannot be changed.
• You can set both the lower and upper display limits when you
have selected custom engineering units (EUF) and the
transmitter output conformity is set to LINEAR.
When setting the lower and upper display limits, if you let either the
lower or upper display limit setting time out (after thirty seconds), the
meter will discard the newly set values and will revert to its previous
settings. The meter forces you to set both limits by automatically
initiating the next limit setting, either lower or upper, depending upon
which limit you set first.
3. If you change the transmitter's output conformity, you must
reconfigure the smart meter as outlined in Tables A-5, A-7 and A-8.
Table A-4
Smart Meter Engineering Units Code
Smart Meter Code
EU0
EU1
EU2
EU3
EU4
EU5
EU6
EU7
EU8
EU9
EUA
EUB
EUC
EUD
EUE
EUF
*
These selections have indicators on smart meter display.
Use stick-on labels provided for other engineering units.
ST 3000 Release 300 Installation Guide
Engineering Unit
%
*
Linear or Square Root
in H 2 O
*
mmHg
*
PSI
*
kPa
MPa
mbar
bar
g/cm 2
kg/cm 2
mmH 2 O
inHg
mH 2 O
GPM
*
GPH
*
Custom
Linear or Square Root
Continued
Transmitter Output
Conformity
Linear
Square Root
Square Root
2/05