Table 5-5 Pv Status; Table 5-6 Device Status - Honeywell OneWireless XYR 6000 User Manual

Isa100.11a compliant pressure transmitter
Hide thumbs Also See for OneWireless XYR 6000:
Table of Contents

Advertisement

5. Operation
5.3. Transmitter PV display
PV status
(blank)
BAD
UNC
Transmitter
OneWireless User
display
Inteface display
OUT SVC
OOS
SENS ERR
Sensor Error
CHAR ERR
Characterization Error
OVR TEMP
Over Temperature
22
OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual

Table 5-5 PV status

PV is normal – no action required
Possible calibration error – Clear calibration
AITB can not execute due to internal firmware state – Attempt cold restart of
device.
AITB can not execute due to hardware fault – Replace sensor board
Sensor failure – Check Connection between Sensor board and Meter Body.
Meter Body Characterization Data is Bad – Replace Meter Body
Meter Body A/D Failure – Replace Meter Body
Meter Body Sensor Fail – Replace Meter Body
Configuration is bad – Check possible units and range settings for input type
and correct AITB configuration.
Hardware fault detected - Replace sensor board
Warning: Calibration (zero or trim) is causing excessive adjustment to
characterization value.
Warning: Input inaccurate due to uncertain input data integrity.
Warning: Input inaccurate due to input conversion limitations or resolution.
Warning: Input outside of characterized range. Value is estimated.

Table 5-6 Device status

Definition
All channels are out of
service.
Sensor can not access
meter body A/D
converter.
Sensor can not access
meter body
characterization or the
characterization is
invalid.
The meter body has
exceeded the maximum
temperature as defined
by the meter body
characterization data.
Cause - Action
What to do
Restore mode to Auto in
OneWireless User Inteface.
Check connection between sensor
module and meter body. If still
doesn't work, replace sensor. See
page 38.
Check connection between sensor
module and meter body. If still
doesn't work, replace sensor. See
page 38.
Determine cause excessive
temperature.
Revision 3