Example
TwinCAT 2:11 b1539 and a BK1120 with firmware B8 were used in the following example.
In an existing configuration (scanned or manually created), the user scaling (offset) of the KL3314 is to be
changed in the startup list of the BK1120 coupler in order to ensure that the desired scaling is also saved in
the terminal in the event of the terminal being exchanged.
2 entries have already been created: selection of terminal 3 and setting of the code word.
Now the user scaling (offset) will be set in register 33 (see terminal documentation). A right click opens the
"Insert" dialog.
Fig. 36: Insert dialog
The following is to be entered in the dialogue
• The state transition P -> S
• the sub-index as register number + 1
in this case: Register 33
• the hexadecimal register value as a byte pair, the high-order byte first
in this case: Set value 1234
BK11x0, BK1250
= Subindex 22
dec
hex
= 04D2
dec
hex
Version: 4.1
Parameterization and commissioning