Danfoss VLT Midi Drive FC 280 Design Manual page 81

Hide thumbs Also See for VLT Midi Drive FC 280:
Table of Contents

Advertisement

Specifications
37
Control
38
33
Functional
isolation
RS485
Illustration 7.1 Galvanic Isolation
NOTICE
HIGH ALTITUDE
For installation at altitudes above 2000 m (6562 ft), contact Danfoss hotline regarding PELV.
Pulse inputs
Programmable pulse inputs
Terminal number pulse
Maximum frequency at terminal 29, 33
Maximum frequency at terminal 29, 33
Minimum frequency at terminal 29, 33
Voltage level
Maximum voltage on input
Input resistance, R
i
Pulse input accuracy (4–32 kHz)
Digital outputs
Programmable digital/pulse outputs
Terminal number
Voltage level at digital/frequency output
Maximum output current (sink or source)
Maximum load at frequency output
Maximum capacitive load at frequency output
Minimum output frequency at frequency output
Maximum output frequency at frequency output
Accuracy of frequency output
Resolution of frequency output
1) Terminal 27 can also be programmed as input.
The digital output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Analog outputs
Number of programmable analog outputs
Terminal number
Current range at analog output
Maximum resistor load to common at analog output
Accuracy on analog output
Resolution on analog output
The analog output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
MG07B102
Design Guide
PELV isolation
Mains
High
Motor
voltage
DC bus
Danfoss A/S © 03/2016 All rights reserved.
29, 33
32 kHz (push-pull driven)
5 kHz (open collector)
4 Hz
See the section on digital input
28 V DC
Approximately 4 kΩ
Maximum error: 0.1% of full scale
0–24 V
40 mA
1 kΩ
10 nF
4 Hz
32 kHz
Maximum error: 0.1% of full scale
10 bit
0/4–20 mA
500 Ω
Maximum error: 0.8% of full scale
10 bit
7
7
2
1
1)
27
1
42
79