3. HYDRAULIC SYSTEMS

ATTENTION:
Before placing the burner in operation,
ensure that the return line is open. Any
obstruction may demage the pump seal.
P 140-200-300 T/G
L meters
H
meters
øi
14 mm
0
20
0,5
25
1
30
1,5
35
2
40
Pay attention to do not overcome the max. depression of
0.45 bar (35 cm Hg), over this value the fuel may turn into gas.
Check the pipes are perfectly sealed.
When the fuel tank is under the burner level we suggest to
let the return line arrive where the suction line starts. In this
case the foot valve is not necessary.
Should the return line arrive over the fuel level, the foot
valve is indispensable. Notice that this solution is less safe
than the previous one, because it is possible the valve has
not a good sealing.
P 140-200-300 T/G
L meters
H
meters
øi
14 mm
0
50
0,5
40
1
30
1,5
20
2
10
3
5
H = Difference in the pipes heights;
L = Total lenght of the suction tube;
= Internal diameter of the tube. Copper tubes ø
ø
i
could be replaced by steel tubes G 1/2" ; copper tubes
ø
16 and 18 mm could be replaced by steel tubes
i
G 3/4 ".
P 450 T/G
L meters
øi
øi
16 mm
16 mm
40
20
45
25
50
30
55
35
60
40
P 450 T/G
L meters
øi
øi
16 mm
16 mm
60
20
50
18
40
15
30
13
20
10
10
5
øi
18 mm
40
45
50
PUMP PRIMING:
Loose the tap from the vacuometer plug (5, fig.1)
55
and wait for the flow of the fuel.
60
øi
18 mm
40
35
30
25
20
10
14 mm
i
32
PUMP PRIMING:
Fill the pump with the light oil
from the vacuometer plug
(5, fig.1), put the burner in
operation, purge the air from the
manometer plug (4, fig.1) and.
wait for the pump priming.
If lock-out occurs repeat the
procedure