Building Technologies
HVAC Products
3.3 Setting up the individual bus
users
3.3.1

Setting up the controllers

3.3.1.1
General remark
Each controller is given an unambiguous identification in the
form of the segment and the device number, because every
address in an LPB system may only be assigned once.
The addressing guidelines are described in Data Sheet
N2030 (Basic System Data).
3.3.1.2
Operating steps on the controllers
1.
Turn off the controller's power supply.
2.
Remove the controller's LPB connection.
3.
Apply power again. Do not yet connect the LPB.
4.
Address the controller on operating lines Segment
number and Device number.
Type of
controller
RVP3..., RVL4...
RWI65.01
RWI65.02
RVD2...
RVP5...
RVA...
5.
For all controllers, set parameter Bus power supply on
the relevant operating line to "Off"
Type of
controller
RVP3.../RVL4...
RWI65.01
RWI65.02
RVD2...
RVP5...
RVA...
User Manual OCI600
Local setting up
Operating line
for segment
number
170
79
68
132
851
851
Operating line for bus power
supply
179
83
72
134
852
852
Operating line
for device
number
169
78
69
131
850
850
74 319 0002 0 c
15.07.2005