The inputs of "Input module 1" through "Input module 4" of
"Log. inputs OCI600" and "Inputs OCI600" (digital inputs) can
be switched to the 2 "Outputs OCI600" (digital outputs).
If the states of several inputs are forwarded to the same re-
lay, the relay will stay active until all inputs are inactive. This
way, a common alarm can be implemented.
A relay used in this way cannot simultaneously be controlled
manually or by a 7-day program. Control via inputs has the
highest priority.
4.2.8

Parameterizing the logical inputs

The 4 "Logical inputs of the OCI600" have the following de-
fault meaning:
Input
1: Communication
error
2: LPB device fault
3: Sensor fault
4: SYNERGYR fault
1)
The controller delivers an alarm message to the bus only if the priority of
its own fault is sufficient
User Manual OCI600
Setting up the OCI600 with the ACS7.. software
Meaning
Here, the response of the OCI600
to an internal fault in the OCI600
itself is parameterized (error code
80-99).
Here, the response of the OCI600
to an alarm message delivered by
a controller connected to the LPB
and entered in the OCI600 is pa-
1)
rameterized.
Here, the response of the OCI600
to an error message delivered by
a temperature sensor connected
to the bus is parameterized.
Here, the response of the OCI600
to an error message delivered by
an OZW30 central unit connected
to the bus is parameterized.
74 319 0002 0 c
15.07.2005