Sending Alarms To The Acs7 - Siemens OCI600 User Manual

Central communication unit
Table of Contents

Advertisement

Procedure
Note on ACS
Service and
ACS Operation
Building Technologies
HVAC Products
5.4.2

Sending alarms to the ACS7...

connected via modem
1.
If there is a direct connection between PC and OCI600,
cut it.
2.
Connect your modem to the OCI600 and check power
supply and wiring to the OCI600 and the telecommuni-
cation network.
3.
On the OCI600, on line number 11 of operating card 3,
set the following parameter:
1 = communication via modem.
4.
Connect your second modem to the PC and check power
supply and wiring to the telecommunication network and
the COM port.
5.
Start ACS Alarm via the ACS Alarm icon on your desk-
top or via Start > Programs > ACS > ACS Alarm.
6.
Open the Extras > Connections... menu.
7.
Select the line with your modem entry and close by choo-
sing "Supervise" and "OK".
8.
Create a new plant, if necessary.
9.
Start with ACS Operation – [Popcard].
Note: The entire setup can be made with ACS Service.
Opening a communication via modem is only possible
with ACS Operation.
10. From the ACS7.. menu, select Plant > Plant proper-
ties...
11. Choose Continue to go to the Communication menu.
12. Go to "Connection" to select your modem.
13. Enter your plant's phone number in the "Phone no.
plant:" field.
Important: The phone number is possibly preceded by
an 0 for an outside line.
14. Choose menu item Plant > Connect.
15. Status window "Connection information" appears. This
window shows the current state of communication build-
up. When the window disappears, communication is
opened.
User Manual OCI600
Communication and delivery of alarms
59/72
74 319 0002 0 c
15.07.2005