Emerson Numatics DeviceLogix G2-2 Series Quick Start Manual page 3

Table of Contents

Advertisement

Available languages

Available languages

MCM Settings
DIP Switch Settings (SW1)
Baud Rate:
SW1-1
Off*
Off
On
On
Autobaud:
Switch
SW1-4
SW1-4
Manual or Software Configuration:
Switch
SW1-5
SW1-5
DIP Switch Settings (SW2) – No Function
Rotary Switch Settings (SW3 and SW4)
MAC ID (Network Address):
Switch
SW3
SW4
G2-2 Series DeviceLogix Quick Start Manual
SW1-2
Kbaud
Off*
125*
On
250
Off
500
On
500
Setting
Autobaud Enabled (baud rate configures automatically for 125Kbps,
Off*
250 Kbps, and 500 Kbps)
Autobaud Disabled (set the baud rate manually either through switches or
On
software)
Setting
Off
MCM Disabled - Ignore MCM Settings (Software Configured)
On*
MCM Enabled - Use MCM Settings (Manually Configured)
Description
Sets the Ones Digits
Sets the Tens Digits
Address is set to a default setting of 63 prior to shipment. Rotary switch
settings over 63, default to 63
DIP and rotary switch settings do not take effect until power is cycled
(turned OFF and ON).
3835054 TDG22DLQS3-0
Subject to change without notice
www.numatics.com/fieldbus
Description
Description
*Factory Default Settings
1/07
Page 3

Advertisement

Table of Contents
loading

Table of Contents