■ R3Di [X] FUNCTIONAL BLOCKS
TYPE
NETWORK
{Range}
VARIABLE
{Default}
nvoDich01
SNVT_switch
through
{0 or 1}
nvoDich16
{0}
nvoDiState
SNVT_state
{0 or 1}
{0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0}
■ R3Do [X] FUNCTIONAL BLOCKS
TYPE
CONFIGURATION
{Range}
PROPERTY
{Default}
nviDoch01
SNVT_switch
through
{0 or 1}
nviDoch16
{0}
nvoDoState
SNVT_state
{0 or 1}
{0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0}
TRANSMISSION DATA ASSIGNMENTS
The DIP SW located at the side of the module specifies each I/O module's data allocation (occupied data area).
Data are assigned in turn from Slot 1, in order of Functional Blocks (Input or GetValue/R3Di first, followed by Output or
SetValue/R3Do).
The 1st output must be the 1st transmitted data in the slot next to the one with the last input data.
[Example 1]
Module 1
Module 2
Module 3
Module 4
Module 5
Module 6
Module 7
Module 8
Module 9
Module 10
[Example 2]
Module 1
Module 2
Module 3
Module 4
Module 5
Module 6
When the data consist of only inputs or outputs, data for the total of 16 Functional Blocks (GetValue [0 – 15] or R3Di [0 – 2],
or SetValue [0 – 15] or R3Do [0 – 2]) are assigned to each module position from Slot 1.
EXPLANATIONS
Data acquired from discrete input channels.
nvoDich01 through nvoDich16 are assigned respectively to channels
1 through 16.
Indicates contact status for each module/slot.
Bit 0 through bit 15 are applied for channels 1 through 16.
EXPLANATIONS
Outputs data set to discrete output channels.
nviDoch01 through nviDoch16 are assigned respectively to channels
1 through 16.
Indicates contact status for each module/slot.
Bit 0 through bit 15 are applied for channels 1 through 16.
Data Area
4
GetValue [0 – 3]
4
GetValue [4 – 7]
4
SetValue [0]
1
SetValue [1]
1
SetValue [2]
1
SetValue [3]
1
SetValue [4]
1
SetValue [5]
1
SetValue [6]
1
SetValue [7]
Data Area
1
GetValue [0]
4
GetValue [1 – 4]
4
GetValue [5 – 7] The 4th data, Slot 3 is invalid.
1
SetValue [0]
4
SetValue [1 – 4]
4
SetValue [5 – 7] The 4th data, Slot 6 is invalid.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
R3-NL1
EM-8427 Rev.7 P. 9 / 9