■ GetValue [x] FUNCTIONAL BLOCKS
TYPE
NETWORK
{Range}
VARIABLE
{Default}
nvoVal
SNVT_lev_percent
{-163.840 through 163.830}
{Depends on cpNvoDefValue}
SNVT_state
{0 OFF (input open)
1 ON (input shorted)}
SNVT_temp
{-274.0 through 3002.7}
TYPE
CONFIGURATION
{Range}
PROPERTY
{Default}
cpNvoType
SCPTnvType
{SNVT_lev_percent
SNVT_state
SNVT_temp}
{SNVT_lev_percent}
cpNvoMaxRnge
Identical to nvoVal
{ (Identical to nvoVal) }
{100.0}
cpNvoMinRnge
Identical to nvoVal
{ (Identical to nvoVal) }
{0.0}
cpSendDelta
Identical to nvoVal
{ (Identical to nvoVal) }
{0.0}
■ SetValue [x] FUNCTIONAL BLOCKS
TYPE
NETWORK
{Range}
VARIABLE
{Default}
nviVal
SNVT_lev_percent
{-163.840 through 163.830}
{0}
SNVT_state
{0 OFF (output open)
1 ON (output shorted)}
TYPE
CONFIGURATION
{Range}
PROPERTY
{Default}
cpNviType
SCPTnvType
{SNVT_lev_percent
SNVT_state}
{SNVT_lev_percent}
cpNviMaxRnge
Identical to nviVal
{ (Identical to nviVal) }
{100.0}
cpNviMinRnge
Identical to nviVal
{ (Identical to nviVal) }
{0.0}
EXPLANATIONS
• Data acquired from assigned channels.
• Set SNVT_lev_percent for the input types other than discrete or
temperature. Change the network variable type according to the
input type if necessary.
• Configuration Property value must be re-read after the network
variable type is changed. Use "ResyncCP" on the LonMaker.
• For discrete inputs, change the network variable type to SNVT_
state using integration tools such as LonMaker.
Bit 0 through bit 15 of nvoVal are applied for ch. 1 through ch. 16.
• For temperature inputs, change the network variable type to
SNVT_temp using integration tools such as LonMaker.
EXPLANATIONS
nvoVal type
(Use integration tools such as LonMaker to change types.)
nvoVal value at 100% input
Invalid when nvoVal type is either SNVT_state or SNVT_temp.
nvoVal value at 0% input
Invalid when nvoVal type is either SNVT_state or SNVT_temp.
Network variables are sent out when its deviation exceeds the set
value.
Invalid when nvoVal type is SNVT_state.
EXPLANATIONS
• Outputs data set to assigned channels.
• Set SNVT_lev_percent for the input types other than discrete.
Change the network variable type according to the output type if
necessary.
• Configuration Property value must be re-read after the network
variable type is changed. Use "ResyncCP" on the LonMaker.
• For discrete outputs, change the network variable type to SNVT_
state using integration tools such as LonMaker.
Bit 0 through bit 15 of nviVal are applied for ch. 1 through ch. 16.
EXPLANATIONS
nviVal type
(Use integration tools such as LonMaker to change types.)
nviVal value at 100% output
Invalid when nviVal type is SNVT_state.
nviVal value at 0% output
Invalid when nviVal type is SNVT_state.