INSTRUCTION MANUAL
L
W
ON
ORKS
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
the contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System's Sales Office or representatives.
PACKAGE INCLUDES:
Network interface module .......................................... (1)
Neuron ID label .......................................................... (2)
MODEL NO.
Check that model No. described on the specification label is
exactly what you ordered.
INSTRUCTION MANUAL
This manual describes necessary points of caution when you
use this product, including installation, connection and basic
maintenance procedures.
POINTS OF CAUTION
POWER INPUT RATINGS
• Operational range & power consumption: Check the power
rating for the unit on the specification label.
Rating 100 – 120V AC: 85 – 132V, 47 – 66 Hz, approx. 20VA
Rating 200 – 240V AC: 170 – 264V, 47 – 66 Hz, approx. 20VA
Rating 24V DC: 24V ±10%, approx. 12W
UNPLUGGING THE UNIT
• Before you remove the unit from its base or mount it, turn
off the power supply for safety.
ENVIRONMENT
• Indoor use
• When heavy dust or metal particles are present in the air,
install the unit inside proper housing with sufficient ventila-
tion.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 30 to 90% RH in
order to ensure adequate life span and operation.
WIRING
• Do not install cables (power supply, input and output) close
to noise sources (relay drive cable, high frequency line, etc.).
• Do not bind these cables together with those in which noises
are present. Do not install them in the same duct.
AND ....
• The unit is designed to function as soon as power is
supplied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data sheet.
INTERFACE MODULE
MODEL
INSTALLATION
Use the Installation Base Model R3-BSx, or Model R3-BSWx
for free I/O address capability.
Before mounting the Network Interface Module onto the
Base, be sure to configure the module as explained below.
DATA ALLOCATION
The setting determines the data area size assigned to each I/
O module mounted on the base.
NETWORK SLOTS ON THE BASE
I/O 1
I/O 2
With Model R3-BSx base, mount the I/O Modules from the
left end (I/O 1) to the right in order that the Network Module
assigns data areas from I/O 1.
Network Module(s) and Power Module are mounted basically
at the right end though technically they could be mounted in
any position.
With Model R3-BSWx base, there is no limitation in mount-
ing positions as I/O address can be assigned freely to each
module using rotary switches equipped on the base.
R3-NL1
R3-NL1
I/O n
P. 1 / 8
EM-8427 Rev.5