SURFACE MOUNT DUAL SENSE DALI SENSOR HIM13
1. Technical Specifications
Product type
Dual sense DALI sensor ( HF and PIR, Tri-level control )
Operating voltage
9.5~22.5VDC (suitable DALI power supply)
Input current
Approx.12mA
Power consumption
0.25W
o
Detection angle
360
Detection area (DxH)
12 x 6m (Maximum)
Mounting height
6m (Maximum)
Detection range
10% / 50% / 75% / 100%
Hold time
2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min
Stand-by time
0s / 10s / 1min / 5min / 10min / 30min / 1h / +∞
Stand-by dimming level
10% / 20% / 30% / 50%
Daylight threshold
2Lux /10Lux / 50Lux / Disable
Warmming up time
30s
o
Operating temperature
-20
C ~ +50
Sensor mode
PIR, HF, PIR+HF, PIR / HF

3. Rotary Switch Settings

A rotary switch is built inside the sensor for
scene selection / fast programming. Total
16 channels available:
Detection
Hold
Channel
range
time
0
100%
5s
1
100%
1min
2
100%
5min
3
100%
5min
4
100%
5min
5
100%
5min
6
100%
5min
7
100%
10min
8
100%
10min
9
100%
10min
A
100%
10min
B
75%
10min
C
50%
10min
D
100%
30min
E
100%
30min
F
100%
5s
Note: settings can also be changed by remote control HRC-11. The last action controls.

5. DALI group selection

DALI group configuration can be done on PC or on the rotary switch:
1. There are 16 channels available on the rotary switch. "0" is
for DALI broadcast, the rest 15 channels is for end user to
define the application unit.
2. PC grouping can overwrite rotary switch grouping, and vise
versa. The last setting controls.
The rotary switch channel is corresponding to the groups listed below:
Switch channel
DALI group
0
broadcast
1
group 0
2
group 1
3
group 2
4
group 3
5
group 4
6
group 5
7
group 6
Installation and Instruction Manual
o
C
Rotary switch preset (Please
see the location in 2. Installation)
Stand-by
Stand-by
time
dimming level
10s
10%
5min
10%
10min
10%
30min
10%
0s
Disable
+∞
10%
+∞
30%
10min
10%
30min
10%
+∞
10%
+∞
30%
+∞
10%
+∞
10%
+∞
10%
+∞
30%
10s
10%
DALI group selection (Please
see the location in 2. Installation)
Switch channel
DALI group
8
group 7
9
group 8
A
group 9
B
group 10
C
group 11
D
group 12
E
group 13
F
group 14

2. Installation

Warnings:
1. Installation must be carried out by a
qualified engineer in accordance with
local regulations.
2. Disconnect supply before installing.
3. Install to a solid surface - vibrations may
cause mis-triggering.
4. Ensure environmental conditions are
suitable for electronic equipment
Note: the blinds are optional, they may be inserted behind the lens for focussing the detection range.
56
Daylight
Direct junction "J" box mounting
threshold
a. Separate control board (A) from facia (B)
Disable
& junction box (C).
2Lux
b. Make electrical connections to control board
(A). See detailed wiring diagram on next page.
10Lux
c. Secure control board (A) to junction box.
30Lux
d. Set-up sensor modes as per sections 3 & 4
10Lux
of this manual.
30Lux
e. Clip facial plate (B) to control board (A).
Disable
2Lux
10Lux
30Lux
Disable
30Lux
10Lux
50Lux
Disable
2Lux

4. Sensor Mode Selection

Sensor mode can be easily selected by choosing the correct combination of the DIP switches
(see table below):
C - Surface box
B - Facia Cover
Infrared receiver
HF Sensor module
Blind
A
DALI group selection
Blind
Rotary switch preset
B
Surface mount assembly
a. Separate control board (A) from facia (B) &
Surface box (C).
b. Securely mount surface box (C) to a flat and
solid surface.
c. Make electrical connections to control board
(A). See detailed wiring diagram on next page.
d. Set-up sensor modes as per sections 3 & 4 of
this manual.
e. Secure control board (A) to surface box (C).
f. Clip facial plate (B) to control board (A).
C
56
A
B
1 2
I
HF
II
PIR
III
HF+PIR
IV
HF/PIR
PIR
Photocell
LED indicator
Sensor mode selection
A - Control Board
C
56
A
B
HF+PIR: Light is on when both HF
and PIR sensors are activated.
HF/PIR: Light is on when HF or PIR
sensors are activated.
HIM13-20190104-A1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DUAL Sense HIM13 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Hytronik DUAL Sense HIM13

  • Page 1 Installation and Instruction Manual SURFACE MOUNT DUAL SENSE DALI SENSOR HIM13 2. Installation 1. Technical Specifications Warnings: C - Surface box Product type Dual sense DALI sensor ( HF and PIR, Tri-level control ) Operating voltage 9.5~22.5VDC (suitable DALI power supply) 1.
  • Page 2 DALI system, and do the grouping work without the help of the DALI master and computer interface. More details please refer to section 5. DALI grouping selection. 6.1 Tri-level Control (Corridor Function) Hytronik builds this function inside the motion sensor to achieve tri-level control, for some areas require a DA1 DA2 DA1 DA2 light change notice before switch-off.

Table of Contents