Start-up procedure

Press the ON/OFF button on the control panel to switch on the
boiler: the display will light up.
The initialisation procedure - indicated by the bar - begins.
Initializing.......
Wi-Fi bo
Once the procedure is completed, the display will visualise the
temperatures set for the central heating and domestic hot water
circuits (display confi guration: boiler base).
00/00/00
42°
Press OK to enter Menu
The boiler will request the setting of the date, time and
language. Proceed as indicated in the USER MENU - see the
User's Manual.
00:00
70°
1,5 bar

FIRST IGNITION

CARRY OUT THE DEAERATION CYCLE AND AUTOMATIC
CALIBRATION
1.
Assicurarsi che:
- The gas valve is closed;
- The electrical connection has been properly carried out.
Make sure that, in any case, the green/yellow earthing wire
is connected to an effi cient earthing system;
- Unscrew the cap on the automatic air relief valve;
- The exhaust duct for combustion products should be
suitable and free from any obstructions;
IMPORTANT!
DURING THE CALIBRATION
PROCEDURE AND MEASUREMENT OF
THE CO2 VALUE, IT'S IMPORTANT THAT
THE BOILER WORKS WITH THE FRONT
COVER CLOSED AND THE AIR/ FUMES
DUCTS FULLY ASSEMBLED.
- Any necessary ventilation inlets in the room should be
open (type B installation).
- Check whether the condense trap contains water; if not, it
must be refi lled. If necessary, open the manual air vent on
the main exchanger until complete fi lling.
N.B.: if the boiler will not be used for long
periods, the trap should be fi lled before the
boiler is started up again. It is dangerous
not to refi ll the siphon as fumes may be
released into the environment.
2. Supply static pressure check
Loosen the screw 1 and insert the
pressure gauge connection pipe into
the pipe tap.
The
supply
pressure
correspond to the value established
in relation to the type of gas, for
which the boiler is designed see
Table summarising changes.
ATTENTION!!
THE BOILER CAN NOT BE ACTIVATED IF
THE PRESSURE IS NOT CORRESPONDING
TO THE TABLE SUMMARISING CHANGES.