Anti-Frost Device - Ariston ALTEAS ONE Net Series Installation And Servicing Instructions

Condensing wall-hung gas boiler, including cube room sensor wireless
Table of Contents

Advertisement

Table summarising error codes
Central Heating circuit
Display Description
Overheat
1 01
Pressure Sens Error
1 02
1 03
1 04
Insuffi cient circulation
1 05
1 06
1 07
Insuffi cient water (request fi lling)
1 08
C.H. Flow temp. probe circuit open / short circuit
1 10
C.H. Return temp. probe circuit open / short circuit
1 12
External sensor circuit open / short circuit
1 14
Heating delevery probe problem
1 18
1 P1
Insuffi cient circulation indication
1 P2
1 P3
Insuffi cient water (request fi lling)
1 P4
D.H.W. circuit
2 05 DHW In Probe Open Circuit
Internal P.C.B.'s
3 01 EEPROM error
3 02 Comunication error
3 03 Main P.C.B. error
3 04 Too many (> 5) resets in 15 minutes
3 05 Main P.C.B. error
3 06 Main P.C.B. error
3 07 Main P.C.B. error
3 13 Low Voltage Fault
3 P9 Sched.Maintanace-Call Service
External P.C.B.'s
Zone 1 - Room sensor circuit open / short circuit
4 11
Zone 2 - Room sensor circuit open / short circuit
4 12
4 13 Zone 3 - Room sensor circuit open / short circuit
Ignition and Detecion
No fl ame detected (After 5 times with
5 01
5P6)
5 02 Flame detected with gas valve closed
Flame detected with gas valve closed
5 03
(After 20 seconds with 502)
5 04 Flame lift
5 P3 Flame cut-off
5 P5 Low Gas Pressure Fault
5 P6 Ignition Failed
Air Inlet / Flue gas outlet
Fan Warning - Anomaly in air inlet and / or fl ue gas
exhaust ducts (Boiler switch off the fan works 20
6 11
minutes at maximum).
If the problem is not resolved appears error 612.
Fan Error (speed higher or lower than the
6 12
set values)
Multi-zone Heating
RESET
Zone 1 send sensor defective
X
7 01
7 02 Zone 2 send sensor defective
7 03 Zone 3 send sensor defective
Zone 1 return sensor defective
7 11
Zone 2 return sensor defective
7 12
7 13 Zone 3 return sensor defective
7 22 Zone 2 overheating
7 23 Zone 3 overheating
7 50 All Heating Zones locked
Combustion Control System (CCS)
Calbration Tuning Fault
8 01
8 02 Flame Sensed with Gas Valve Closed
Mismatch kW Size, ID combustion
8 03
(Set parameter 229)
Decoupling Clip-In required (see note)
8 04
NOTE - ERROR 804:
TO CONNECT THE BOILER TO ELECTRONIC
SOLUTIONS FOR SOLAR MANAGEMENT OR
IBRID SYSTEMS (ONLY FOR COMBINATIONS NOT
ADMITTED), IT'S NECESSARY TO INSTALL A CLIPIN
SUPPLIED AS ACCESSORY CODE 3319171.

Anti-frost Device

X
The anti-frost function acts on the central heating fl ow temperature
probe, independently from other regulations, when the electrical
supply is turned on.
X
If the primary circuit temperature falls below 8°C the pump will
run for 2 minutes.
X
After the two minutes of circulation (fi xed) the boiler will check
the following:
a) if the central heating fl ow temperature is > 8°C, the pump
stops;
b) if the central heating fl ow temperature is between 4 and 8°C,
the pump will run for another two minutes;
c) if the central heating fl ow temperature is < 4°C, the burner will
fi re (heating position) at minimum power until the temperature
reaches 33°C, the burner will go out and the pump will continue
to run for two minutes.
The anti-frost device activates only when (with the boiler
operating correctly):
X
- the system pressure is correct;
- the boiler is electrically powered;
- there is a supply of gas.
X
X
BOILER PROTECTION DEVICES
/
37