BOILER PROTECTION DEVICES

Appliance shut-off conditions
The boiler is protected from malfunctions by means of internal
checks performed by the electronic P.C.B., which stops the boiler
from operating if necessary. In the event of the boiler being shut
off in this manner, a code appears on the control panel display
which refers to the type of shut-off and the reason behind it.
Two types of shut-off may occur:
Safety shut-off
This type of error is "volatile", which means that the boiler starts
up again automatically as soon as the problem which caused the
shut-off is removed.
The display shows the code and the error description.
"Fault 110 - Send Probe Damaged"
ALERT
In fact, soon as the cause of the shut-off disappears, the boiler
starts up again and continues to operate normally.
If the boiler still indicates a safety shut-off , switch it off . Make sure
the external electric switch is in the OFF position, shut off the gas
valve and contact a qualifi ed technician.
Safety shut-off due to insuffi cient water pressure
In caso di insuffi ciente pressione dell'acqua nel circuito
riscaldamento la caldaia segnala un arresto di sicurezza.
The display shows "Fault 108 - Filling Needed".
ALERT
If the re-balancing request is performed on a frequent basis,
switch the boiler off , bring the external electric switch to the OFF
position, shut off the gas valve and contact a qualifi ed technician
to check for any leaks of water.
36
/
Fault 110
Send Probe Damaged
Fault 108
Filling Needed
Operation shutdown
This type of error is "non-volatile", which means that it is not
removed automatically.
The display shows the code and the error description.
To restore normal operation press the RESET button on the
control panel.
The dispay shows "Reset in progress" and then "Fault solved".
If the problem manifests itself again after several attempts to
reset the appliance, contact a qualifi ed technician.
Fault 501
ALERT
No flame detected
Press the Reset button
Reset in corso
Important
If this shutdown occurs frequently, contact an authorised Technical
Service Centre for assistance. For safety reasons, the boiler will permit
a maximum of 5 resets in 15 minutes (5 presses of the RESET button);
at the 6th attempt within this 15-minute period the boiler will shut down
and may only be operated again after the electricity supply has been
disconnected. If the shutdown is occasional or an isolated event, this is
not a problem.
The fi rst fi gure of the error code (e.g. 1 01) indicates within which
operational assembly the error occurred.
1 - Primary Circuit
2 - Domestic Hot Water Circuit
3 - Internal Electronic Part
4 - External Electronic Part
5 - Ignition and Detection
6 - Air inlet - fl ue gas outlet
7 - Multizone heating
8 - Combustion Control System
Malfunction warning
This warning is shown by the display in the following format:
5 P3 = Flame cut-off
5 P3
the fi rst fi gure indicating the operational assembly is followed by
a P (warning) and the code relating to the specifi c warning.
Circulation pump malfunction signal
The circulation pump has an LED display that shows its operating
status:
LED off :
The
circulation
pump
is
electrically charged.
LED solid green:
circulation pump enabled.
LED fl ashing green: change
of speed taking place.
LED red:
Circulation pump is blocked
or lacks water.
Fault 501
No flame detected
ALERT
Press the Reset button
Fault solved