Installing the Boiler

Please check that you are familiar with the installation
requirement before commencing work (pages 10 - 14).
The installation accessories described in the following list are
included in the boiler packaging:
- Hanging bracket
- A paper template (showing the dimensions of the boiler with
5 mm side clearances)
- Connection valves (compression)
- Screws and washers
- Filling loop
- Installation, Servicing and User manual
Method of positioning the boiler on the wall
The paper template can be used to ensure the correct positioning
of kitchen cabinets etc.
The paper template has to be fi xed to the wall and used to
locate the position of the hanging bracket and the centre for the
fl ue hole.
Drill and plug the wall and secure the hanging bracket using the
screws provided ensure the hanging bracket is level. Remove
the boiler from its packaging and remove the front casing panel.
Place the boiler on the hanging bracket.
N
: T
OTE
HE APPLIANCE MUST NOT BE FITTED ON A COMBUSTIBLE WALL SURFACE
Connecting the boiler to the system
- Remove the boiler casing as described on page 14
- Remove the caps and connect the valves to the boiler using
the washers provided
- 5 x fi bre washers for the CH fl ow and return, cold water inlet, gas
and hot water outlet connections
Safety Valve Discharge
The pressure relief valve pipe is made of copper. It should
terminate below the boiler safely outside the premises. Care
should be taken that it does not terminate over an entrance or
window or where a discharge of heated water could endanger
occupants or passers by.
WARNING!
DO NOT APPLY HEAT TO THE COPPER
SAFETY VALVE OUTLET PIPE WHILST IT IS
CONNECTED TO THE 3 BAR SAFETY RELIEF
VALVE.
Fill the central heating and DHW system and bleed air from the
system as described in the Commissioning instructions (page
27).
The system should be carefully checked for leaks, as frequent
refi lling could cause premature system corrosion or unnecessary
scaling of the heat exchanger. The pipe from the trap should be
connected to a drain as described in the relevant regulations.
Pay special attention not to bend the condensate silicone drain
pipe is such a way as to interrupt the fl ow. Please only use drain
pipe material compatible with condensate products (refer to BS
6798:2009).
The condensate fl ow can reach 2 litres/hour because of the
acidity of the condensate products (Ph close to 2), take care
before operation.
See page 13 for condensate discharge options.
INSTALLATION
.
/