Dialer Capture Module Information; Led Display Information - Honeywell IPGSM-4GC Installation And Setup Manual

Commercial fire communicator
Hide thumbs Also See for IPGSM-4GC:
Table of Contents

Advertisement

IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide

Dialer Capture Module Information

LED Indicator
RED – Steady ON
RED – Flashing
GREEN – Steady ON
GREEN – Blinks every 2 sec.
GREEN – Blinks twice every sec.
GREEN – Blinks 10 times every sec.

LED Display Information

Status
RADIO TROUBLE
LOW BATTERY
AC LOSS
AC ON
Note: If a wire pulled out of the LED Board Connector
refer to the diagram on right and reinsert wire, ensuring
the connector pin is locked in.
STATUS
Messages exist in buffer.
No messages to be sent. Waiting for messages.
Normal Indication.
PowerBoost1 communication problem.
Connection with the Communicator is lost.
PowerBoost1 and Communicator connections are lost.
RED
GREEN
Dialer Capture Module
LED Indicator
Yellow – ON when radio trouble is present.
Both IP and GSM communication paths are lost.
Communicator radio is not registered.
Old Alarm Time has been exceeded. (Message has not been
delivered within the fixed 10 minute window.)
Buzzer – Upon loss of AC power, this will beep once every 10
seconds.
Yellow – ON when battery is low (<11.5VDC).
Yellow – (not used)
Yellow – ON when no AC is present (< 90VAC).
Green – ON when AC is present.
Note: Telco ports 1 (primary dialer)
and 2 (secondary dialer) may be used
instead of the terminal board.
Whichever connection method is used,
both Telco paths must be connected to
the Fire Panel.
– 9 –
RADIO TROUBLE
LOW BATTERY
Violet
LED Board
Black
Connector
White
Wires
NC
Red
NC
Brown
Yellow
Gray
(not used)
AC LOSS
AC ON