IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide

RF Specifications

Frequency Bands
2G
GSM/GPRS/EDGE
3G/4G
UMTS/HSPA+
Output Power
2G
GPRS
EDGE
3G
UMTS
WCDMA
4G
HSPA+
WCDMA

Central Station Messages

Power On / Reset
ECP Supervision (Compromise Indication)
Primary Communication Path Supervision
Secondary Communication Path Supervision
Periodic GSM Comm Path Test Failure
(We do not send a restoral R358 C0803, we send a failure message every day after
the radio attempts to test and fails.)
Trouble Reporting:
When a single fault (open or short IP, GSM suppression, low/missing battery,
AC loss) occurs, and the communicator is programmed for an IP& GSM
communication path, multiple alarm Codes and their appropriate Restore
Codes are reported to the Central Station.
IPGSM-4GC communicator fault – The Fire Panel sends out a E380, and E352
message via Telco #1, these are then relayed to the central station via the
IPGSM-4GC.
Telco line 1 fault – The Fire Panel sends out a E380, and E351 message via
Telco #2, these are then relayed to the central station via the IPGSM-4GC.
Telco line 2 fault - - Fire Panel sends out a E380, and E352 via Telco #1,
these are then relayed to the central station via the IPGSM-4GC.
Test
Specific to COMMERCIAL Control Panels (Such as the VISTA-32FB, and VISTA-128FBP/250FBP series.)
Communicator Trouble (low battery, ECP bus, network) (Possible
Compromise Indication)
Radio Loss of Signal
(Possible Compromise Indication)
Radio Fault (low battery, tamper, ECP Bus)
AlarmNet Messages
Communication failure.
(Possible Compromise Indication)
Authorized Radio Substitution
Unauthorized Radio Substitution Attempt
Service Termination
Quad Band, 850/900/1800/1900 MHz
Band V, Band II
+33dBm, GMSK modulation
+27dBm, 8-PSK modulation
+24dBm, QPSK modulation
+24dBm, QPSK modulation
+24dBm, 64 QAM modulation
+24dBm, 64 QAM modulation
Alarm Condition
– 12 –
Alarm Code
Restore Code
E339 C0803
N/A
E355 C0000
R355 C0000
E350 C0951
R350 C0951
E350 C0952
R350 C0952
E358 C0803
N/A
E380, E351, E352
N/A
codes as
appropriate.
5555 5555 9
N/A
E333 C0803
R333 C0803
E357 C0803
R357 C0803 or
R380 C0803
E333 C0803
R333 C0803
5555 1555 6
5555 3555 6
00D0 010C 0
N/A
00D0 010E 0
N/A
00D0 020E 0
N/A