A. Full Reline With Outside Air - Horizontal
CAUTION
Never draw outside combustion air from:
Wall, floor or ceiling cavity
Enclosed space such as an attic or garage
Figure 18.1
NOTE:
In Canada, where passage through a wall or partition of
combustible construction is desired, the installation shall
conform to CAN/CSA-B365.
18
NOTE; Use metal plate around
exhaust vent pipe and seal all
edges with non-flammable insu-
lation such as mineral wool or
ceramic.
Do not use high temperature
caulking materials to seal any
edge to prevent furture service-
ability.
Fire Risk.
Inspection of Chimney:
Masonry chimney must be in good condition.
Meets minimum standard of NFPA 211
Factory-built chimney must be a minimum 6
inch (152mm) UL103 HT.
Outside Air through Rear
Wall (Horizontal)
NOTE:
Illustrations reflect typical installations and are FOR
DESIGN PURPOSES ONLY.
Illustrations/diagrams are not drawn to scale.
Actual installation may vary due to individual design
preference.
7014-285C
WARNING
August 1, 2018