The PLC-16.PCI provides two parallel input/output (I/O) ports. The ports are organized as ports A, B, C, and D.
Port A is an input port interfaced to optically isolated inputs, while port C is the relay output port.

Features

Digital Inputs

Number of inputs: Eight.
Type: Non-polarized, optically isolated from each other and from the computer.
Voltage Range: 5 to 24V DC or AC.

Relay Outputs

Number of outputs: Eight.
Contact Rating: 2A carry current, bifurcated, gold clad, silver palladium.
Contact Arrangement: SPDT (Single Pole Double Throw) Form C.
Contact Resistance: Initial 100 milliohms maximum.
Contact Life: mechanical: 10 million operations minimum.
Contact Life: electrical: 5 million operations minimum at full load.
Operating Time: 2 milliseconds maximum.
Release Time: 1 milliseconds maximum.