Setting The F-Address - YASKAWA VIPA SLIO SDI Operating Manual

Safety digital i/o
Table of Contents

Advertisement

VIPA System SLIO

3.3 Setting the F-address

Address switch for F-
address
HB300 | SM-S | 02x-1SD10 | en | 20-02
The F-address respectively "Secure user address" is to be configured by the F-address
switch at the safety module and additionally in the master system e.g. hardware configu-
rator. The F-address is to be set by the F-address switch besides on the safety module.
Only if the F-address set in the hardware configurator accords to the setting of the F-
address switch, it is possible to operate!
Pos
Value
0
1
1
2
2
4
3
8
4
16
5
32
6
64
7
128
8
256
9
512
10
1024
11
2048
When the safety module is installed, the F-address switch may not
be accessed!
To set the F-address on the safety module the (electronic) module is to
be demounted before as described at "Demounting and module
Ä Chap. 3.5 'Demounting and module exchange' page 80
exchange".
n
Before setting take the field bus coupler of circuit!
n
F-address must be unique!
F-addresses from 1 to 4095 may be set.
Each F-address must be unique in the communication network of the safety PLC!
Only use suitable tools for the setting!
n
The switching elements of the F-address switch must be set only with a suitable
tool like a screwdriver of a clockmaker.
In no case should pressure be exerted on the switching elements.
n
Setting the F-address via safety parameter dialog
In addition the F-address setting of the F-address switch must be configured by
the safety parameter dialog of the master system.
Example
State
Address
1
1
0
0
0
1
1+2+32+512=547
Address: 547
0
0
0
1
0
0
Deployment
Setting the F-address
71